| Plan Review Notes For Permit 16060825 |
| Permit Number |
16060825 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-08 13:52:37 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: FOUNDATION PERMIT ONLY | | | | | | 1. E-001- UPDATE ELECTRICAL CODE ANALYSIS TO REFLECT | | | NEC 2011 NOT 2014 AS SHOWN. FBC 107.3.5 | | | 2. E502- PROVIDE A GENERAL NOTE TO INDICATE REQUIRED | | | SEPARATE PERMIT REQUIRED FOR THE LIGHTING PROTECTION | | | WITH ALL ASSOCIATED DOCUMENTATION. | | | 3. E1.01- PROVIDE A NOTE TO INDICATE NEC 300.5 BURIAL | | | DEPTHS AND ALSO A NOTE THAT NO BACKFILL IS TO BE | | | PERFORMED BEFORE ANY FIELD INSPECTIONS. | | | 4. PROVIDE THE ELECTRICAL RISER SHEET SHOWING THE SIZE | | | OF THE GROUNDING ELECTRODE CONDUCTOR TO FOOTER (BOND). | | | 5. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|