2016-07-08 13:52:37INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS: FOUNDATION PERMIT ONLY
  
 1. E-001- UPDATE ELECTRICAL CODE ANALYSIS TO REFLECT
 NEC 2011 NOT 2014 AS SHOWN. FBC 107.3.5
 2. E502- PROVIDE A GENERAL NOTE TO INDICATE REQUIRED
 SEPARATE PERMIT REQUIRED FOR THE LIGHTING PROTECTION
 WITH ALL ASSOCIATED DOCUMENTATION.
 3. E1.01- PROVIDE A NOTE TO INDICATE NEC 300.5 BURIAL
 DEPTHS AND ALSO A NOTE THAT NO BACKFILL IS TO BE
 PERFORMED BEFORE ANY FIELD INSPECTIONS.
 4. PROVIDE THE ELECTRICAL RISER SHEET SHOWING THE SIZE
 OF THE GROUNDING ELECTRODE CONDUCTOR TO FOOTER (BOND).
 5. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
  