| Plan Review Notes For Permit 16060797 |
| Permit Number |
16060797 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-16 08:46:00 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | - C405.2.4 EXTERIOR LIGHTING CONTROLS. | | | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. | | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | | FOR A PERIOD OF AT LEAST 10 HOURS. | | | | | | - DIAGRAM DOES SHOW A DISCONNECT WITHIN SIGHT IN | | | ACCORDANCE WITH NEC 600.6 BUT PLEASE ADD A NOTE STATING | | | THE DEDICATED 20 AMP CIRCUIT IS EXISTING TO BE RE USED | | | PER NEC 600.5 | | | | | | - ALL GROUNDING AND BONDING REQUIREMENTS SHALL COMPLY | | | WITH NEC 600.7(A)(B) |
|