2016-06-23 10:44:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS AND
 WINDOW TYPE, FBC R310, EB 704.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5% (SLEEPING ROOMS).
  
 TWO DIFFERENT WINDOW PRODUCT APPROVALS WERE SUBMITTED
 (HORIZONTAL ROLLER, SINGLE HUNG). PROPOSED LOCATION OF
 EACH IS NOT CLEAR. ROOM DESIGNATIONS WERE NOT PROVIDED,
 SO IT IS NOT CLEAR WHETHER OR NOT SLEEPING ROOM
 REQUIREMENTS ARE APPLICABLE.
  
  