Plan Review Notes
Plan Review Notes For Permit 16060763
Permit Number 16060763
Review Stop B
Sequence Number 1
Notes
Date Text
2016-06-25 13:27:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLANS ARE LABELED TENANT BUILDOUT FOR AZURE DETOX.
 THIS CONFLICTS WITH THE APPLICATION. FBC 107, PLAN
 TITLE BLOCK SHOULD BE CONSISTENT WITH WORK PROPOSED.
  
 2. PLANS SUBMITTED INCLUDE A PHOTOCOPY SIGNATURE. PER
 FS481, THE SIGNATURE IS TO BE AN ORIGINAL (UNLESS AN
 EXCEPTION FOR THIS ARCHITECT HAS ALREADY BEEN MADE BY
 THE BOARD).
  
 3. HOW WILL THE BUILDING BE SECURED IF ALL OF THE
 WINDOWS ARE REMOVED? FBC 107. PLANS INCLUDE A WINDOW
 SCHEDULE, BUT NO PRODUCT APPROVALS WERE PROVIDED AND
 THE APPLICATION DOES NOT INCLUDE THIS SCOPE.
  
 4. IT APPEARS THAT A CHANGE OF OCCUPANCY MAY BE
 REQUIRED. WINDOW EMERGENCY ESCAPE AND RESCUE OPENINGS
 MAY BE APPLICABLE. NOT ENOUGH INFORMATION HAS BEEN
 PROVIDED FOR A COMPLETE REVIEW, FBC CHAPTER 10, FBC
 107.
  
 5. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
  
  
  