| Plan Review Notes For Permit 16060733 |
| Permit Number |
16060733 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-14 04:22:53 | 1) SUBMIT A SET OF PLANS THAT CLEARLY SHOWS THE | | | LOCATION IN THE UNIT WHERE THE WORK IS BEING DONE.WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 2) THE TUB FAUCET VALVE SHALL BE BALANCED - PRESSURE, | | | THERMOSTATIC OR COMBINATION BALANCED-PRESSURE / | | | THERMOSTATIC VALVE THAT COMPLIES WITH ASSE 1016 OR ASME | | | A112.18.1.THE MAXIMUM TEMPERATURE OF THE WATER SHALL BE | | | LIMITED TO 120 DEGREES F.2014 FPC SEC.424.3. | | | 3) IF A WATER - TEMPERATURE LIMITING DEVICE IS USED IT | | | SHALL CONFORM TO ASSE 1070 OR CSA B125.3. 2014 FPC | | | SEC.424.5. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|