| 2016-06-13 10:02:46 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| | |
| | 553.792?BUILDING PERMIT APPLICATION TO LOCAL |
| | GOVERNMENT.? |
| | (1)?WITHIN 10 DAYS OF AN APPLICANT SUBMITTING AN |
| | APPLICATION TO THE LOCAL GOVERNMENT, THE LOCAL |
| | GOVERNMENT SHALL ADVISE THE APPLICANT WHAT INFORMATION, |
| | IF ANY, IS NEEDED TO DEEM THE APPLICATION PROPERLY |
| | COMPLETED IN COMPLIANCE WITH THE FILING REQUIREMENTS |
| | PUBLISHED BY THE LOCAL GOVERNMENT. |
| | |
| | YOUR APPLICATION IS INCOMPLETE AS NO PLAN IS PROVIDED |
| | RATHER ONLY A WRITTEN SCOPE OF WORK HAS BEEN PROVIDED. |
| | AT LEAST A SKETCH SHOWING THE FLOOR PLAN SHOULD BE |
| | INCLUDED TO ALLOW FOR DETERMINATION OF COMPLIANCE AS TO |
| | CLEARENCES OF FIXTURES. |
| | |
| | PROVIDE A PLAN PER FBC 107, MINIMUM PLAN REVIEW |
| | REQQUIREMENTS. |
| | |
| | ADDITIONALLY, PROVIDE A FLOORING UNDERLAYMENT SUBMITTAL |
| | TO INCLUDE PRODUCT TEST REPORTS TO DEMONSTRATE |
| | COMPLIANCE WITH FBC SECTIONS; |
| | 603.1 FLAME SPREAD |
| | 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |