| 2016-06-15 14:08:52 | 1617 NORTH FLAGLER DRIVE #12A | | | PERMIT #16060727 | | | MASTER #16040257 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE A HYDRAULIC CALCULATION SUPPORTING THE 4 | | | SPRINKLERS SUPPLIED BY A 1-INCH BRANCHLINE | | | (BREAKFAST/DINING/KITCHEN AREA). | | | | | | PLAN GENERAL NOTE INDICATES SYSTEM DESIGNED FOR NFPA | | | 13-RESIDENTIAL. NFPA 13R IS LIMITED TO RESIDENTIAL | | | BUILDINGS 4-STORIES OR LESS. | | | | | | INDICATE THE HYDROSTATIC TEST PRESSURE TO BE UTILIZED | | | FOR THE PRESSURE TEST. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|