Plan Review Notes
Plan Review Notes For Permit 16060610
Permit Number 16060610
Review Stop B
Sequence Number 1
Notes
Date Text
2016-06-17 13:35:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060610
 ADD: 1045 CHARLOTTE AVE.
 CONT: T.B.D./ TO BE DETERMINED
 TEL: EXT. 1053 CONTACT; DANIEL ROBERGE
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 17/2016
 ACTION: DENIED
  
 1) SHEET A-02 THE FLOOR PLAN INDICATES NEW ACCESSIBLE
 STALLS IN BOTH THE WOMEN?S AND MEN?S RESTROOMS. THE
 STALLS ARE NOT DIMENSIONED TO THEIR OVERALL WIDTH AND
 LENGTH. COMPLIANCE WITH 2014 FBC-ACCESS. CODE SECTION
 604.3.1 SIZE CANNOT BE DETERMINED. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES
 (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 2) THE OTHER ISSUE WITH THE MEN?S GANGED RESTROOM IS
 COMPLIANCE WITH 2014 FBC-ACCESS. CODE 213.3.1.
 TOILET COMPARTMENTS. WHERE TOILET COMPARTMENTS ARE
 PROVIDED, AT LEAST ONE TOILET COMPARTMENT SHALL COMPLY
 WITH 604.8.1. IN ADDITION TO THE COMPARTMENT REQUIRED
 TO COMPLY WITH 604.8.1, AT LEAST ONE COMPARTMENT SHALL
 COMPLY WITH 604.8.2 WHERE SIX OR MORE TOILET
 COMPARTMENTS ARE PROVIDED, OR WHERE THE COMBINATION OF
 URINALS AND WATER CLOSETS TOTALS SIX OR MORE FIXTURES.
  
 2A) PLEASE SHOW COMPLIANCE WITH THE 2014 FBC-ACCESS
 CODE: 604.8.2.1 SIZE. AMBULATORY ACCESSIBLE
 COMPARTMENTS SHALL HAVE A DEPTH OF 60 INCHES (1525 MM)
 MINIMUM AND A WIDTH OF 35 INCHES (890 MM) MINIMUM AND
 37 INCHES (940 MM) MAXIMUM.
  
 2B) PLEASE SHOW COMPLIANCE WITH THE 2014 FBC-ACCESS
 CODE: 604.8.2.2 DOORS. TOILET COMPARTMENT DOORS,
 INCLUDING DOOR HARDWARE, SHALL COMPLY WITH 404, EXCEPT
 THAT IF THE APPROACH IS TO THE LATCH SIDE OF THE
 COMPARTMENT DOOR, CLEARANCE BETWEEN THE DOOR SIDE OF
 THE COMPARTMENT AND ANY OBSTRUCTION SHALL BE 42 INCHES
 (1065 MM) MINIMUM. THE DOOR SHALL BE SELF-CLOSING. A
 DOOR PULL COMPLYING WITH 404.2.7 SHALL BE PLACED ON
 BOTH SIDES OF THE DOOR NEAR THE LATCH. TOILET
 COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA.
  
 2C) PLEASE SHOW COMPLIANCE WITH THE 2014 FBC-ACCESS
 CODE: 604.8.2.3 GRAB BARS. GRAB BARS SHALL COMPLY WITH
 609. A SIDE-WALL GRAB BAR COMPLYING WITH 604.5.1 SHALL
 BE PROVIDED ON BOTH SIDES OF THE COMPARTMENT.
  
 2D) PLEASE SHOW COMPLIANCE WITH THE 2014 FBC-ACCESS
 CODE: 609.8 STRUCTURAL STRENGTH. ALLOWABLE STRESSES
 SHALL NOT BE EXCEEDED FOR MATERIALS USED WHEN A
 VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS IS APPLIED
 AT ANY POINT ON THE GRAB BAR, FASTENER, MOUNTING
 DEVICE, OR SUPPORTING STRUCTURE.
  
 3A) SHEET M-1 NOTE # 5 INDICATES NEW 100 % OUTSIDE AIR
 UNIT TO REPLACE 2 EXISTING UNITS ON PLATFORMS.
 THIS NEW ROOFTOP UNIT APPEARS TO BE ON A ROOF TOP CURB
 AND NOT ON AN A/C STAND. FOR A NEW RTU A HOLE WILL NEED
 TO BE CUT INTO THE ROOF DECK, PLEASE PROVIDE NEW
 FRAMING DETAIL AND HOW THE NEW FRAMING WILL TIE BACK
 INTO THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM?
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
 FBC-B 1609.6.4 DESIGN PROCEDURE. THE MWFRS AND THE
 COMPONENTS AND CLADDING OF EVERY BUILDING OR OTHER
 STRUCTURE SHALL BE DESIGNED FOR THE PRESSURES
 CALCULATED USING EQUATION 16-35.
  
 3B) THE ROOF TOP CURB WILL ALSO NEED TO BE SECURED TO
 THE ROOF FRAMING AS WELL AS THE NEW RTU TO THE ROOF TOP
 CURB. PLEASE PROVIDE ANCHORING SYSTEM FOR THE CURB AND
 RTU.
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM
 MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED
 TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS?
  
 3C) 2014 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)( C ) WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES & CURBS
 (G) PRE-ENGINEERED A/C STANDS
  
 3D) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 4.2. RISK CATEGORY.
  
 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  