| Notes |
| Date |
Text |
| 2016-06-28 14:03:49 | 1ST REVIEW: FBC 2014 MECHANICAL, ENERGY CONSERVATION | | | PERMIT #16060604 | | | 6/28/16 | | | | | | 1) DUE TO THE INCREASE IN CONDITIONED SPACE, THE NEW | | | 35' X 8' LIVING AREA IS DEFINED AS AN ADDITION PER | | | SECTION 202 FBC-14 ENERGY CONSERVATION, AND SHALL BE | | | BROUGHT INTO FULL COMPLIANCE WITH THE CODE- SECTION | | | C101.4.5 FBC-14 ENERGY CONSERVATION. PLEASE SUBMIT | | | ENERGY CALCULATIONS. | | | | | | 2) SUBMIT AC CCOLING AND HEATING CALCULATIONS FOR THE | | | PROPOSED ADDITION IN COMPLIANCE WITH SECTION C403.2.1 | | | FBC-14 ENERGY CONSERVATION. | | | | | | 3) SHOW ALL PROPOSED AC ALTERATIONS REQUIRED TO PROVIDE | | | CONDITIONING TO THE NEW ADDITION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|