| 2016-06-28 15:50:40 | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | 1. THE APPLICABLE CODE IS THE 5TH EDITION OF THE 2014 |
| | FBC-R. CORRECT NOTE ACCORDINGLY. |
| | 2. FBC-RE4101.5/NEC 422.31(B) YOU SHALL PROVIDE A |
| | DISCONNECT FOR THE WATER HEATER OR MAKE A NOTE AS TO |
| | THE MODE OF COMPLIANCE. |
| | 3. FBC-RE3901.7/NEC 210.52(E)(3) REQUIRES THAT THERE BE |
| | AN OUTLET WITHIN THE PERIMETER OF THE BALCONY. |
| | 4. FBC-RE3903.4/NEC 210.70(3) REQUIRES THAT THERE BE AT |
| | LEAST ONE SWITCH FOR THE ATTIC LIGHT AT THE POINT OF |
| | ENTRY, (IN THE INTEREST OF ENERGY CONSERVATION MAY I |
| | SUGGEST THE SWITCH HAVE A PILOT LIGHT AND BE OUTSIDE |
| | THE ATTIC ON A WALL VISIBLE TO THE OCCUPANTS). THIS |
| | DOES AWAY WITH THE PULL CHAIN AS THE SINGLE SWITCH. |
| | FURTHERMORE, THE ACTUAL LUMINAIRE SHALL CLOSE TO THE |
| | EQUIPMENT. |
| | 5. FBC-RE4003.2/NEC 410.11 REQUIRES THAT LUMINAIRES |
| | NEAR COMBUSTIBLE MATERIALS HAVE A GUARD AROUND THE LAMP |
| | TO PREVENT CONTACT GREATER THAN 90 DEGREES. THIS |
| | ELIMINATES THE EXPOSED LAMP PULL CHAIN FIXTURE IN THE |
| | ATTIC. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |