| Notes |
| Date |
Text |
| 2016-06-15 18:56:44 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | - PLEASE PROVIDE A RISER DIAGRAM SHOWING WIRE SIZE, | | | BREAKER SIZE, AND CONDUIT SIZE OR SPECIFY INFORMATION | | | ON THE FLOOR PLAN WHICH SHOULD BE SITE SPECIFIC AND | | | SHOW LOCATION OF ELECTRICAL EQUIPMENT. IN ADDITION | | | PROVIDE HOT TUB MANUFACTURE SPEC CUT SHEET. FBC 107 | | | | | | - NEC 680.71 PROTECTION. HYDROMASSAGE BATHTUBS AND | | | THEIR ASSOCIATED ELECTRICAL COMPONENTS SHALL BE ON AN | | | INDIVIDUAL BRANCH CIRCUIT(S) AND PROTECTED BY A READILY | | | ACCESSIBLE GROUND-FAULT CIRCUIT INTERRUPTER. ALL | | | 125-VOLT, SINGLE-PHASE RECEPTACLES NOT | | | EXCEEDING 30 AMPERES AND LOCATED WITHIN 1.83 M (6 FT) | | | MEASURED HORIZONTALLY OF THE INSIDE WALLS OF A | | | HYDROMASSAGE TUB SHALL BE PROTECTED BY A GROUND-FAULT | | | CIRCUIT INTERRUPTER. |
|