2016-06-15 18:56:44REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PLEASE PROVIDE A RISER DIAGRAM SHOWING WIRE SIZE,
 BREAKER SIZE, AND CONDUIT SIZE OR SPECIFY INFORMATION
 ON THE FLOOR PLAN WHICH SHOULD BE SITE SPECIFIC AND
 SHOW LOCATION OF ELECTRICAL EQUIPMENT. IN ADDITION
 PROVIDE HOT TUB MANUFACTURE SPEC CUT SHEET. FBC 107
  
 - NEC 680.71 PROTECTION. HYDROMASSAGE BATHTUBS AND
 THEIR ASSOCIATED ELECTRICAL COMPONENTS SHALL BE ON AN
 INDIVIDUAL BRANCH CIRCUIT(S) AND PROTECTED BY A READILY
 ACCESSIBLE GROUND-FAULT CIRCUIT INTERRUPTER. ALL
 125-VOLT, SINGLE-PHASE RECEPTACLES NOT
 EXCEEDING 30 AMPERES AND LOCATED WITHIN 1.83 M (6 FT)
 MEASURED HORIZONTALLY OF THE INSIDE WALLS OF A
 HYDROMASSAGE TUB SHALL BE PROTECTED BY A GROUND-FAULT
 CIRCUIT INTERRUPTER.