| 2016-06-09 13:20:30 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16060596 |
| | ADD: 1447 40TH ST. |
| | CONT: O/B MELVIN WILLIAMS |
| | TEL: 561-644-3437 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JUNE 09/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION UNDER THE HEADING SCOPE OF |
| | WORK INDICATES FLAT ROOF REPAIR. PLEASE EXPLAIN, TO |
| | WHAT PER CENT OF THE ROOF (FLAT DECK) IS BEING REPAIRED |
| | OR IS THIS A ROOF OVER OR IS FLAT DECK ROOFING BEING |
| | REMOVED AND REPLACED. THE PROPERTY APPRAISERS OFFICE |
| | LIST THE FLAT DECK AS 320 SQ. FT. FOR A VALUE OF |
| | $5,000.00 DOLLARS THIS PERMIT SHOULD BE FOR A REROOF, |
| | REMOVAL OF OLD ROOFING MATERIAL AND A NEW FLAT DECK |
| | APPLIED. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) THE PRODUCT APPROVAL A MIAMI-DADE NOA 15-0203.05 A |
| | 17 PAGE APPROVAL WAS SUBMITTED. PAGES 8-16 ARE VARIOUS |
| | SUB-SYSTEMS INSULATED AND NON-INSULATED SYSTEMS AND |
| | ASSOCIATED PRESSURES RANGING FROM -45 TO -60 PSF. ALL |
| | OF THE SUB-SYSTEMS LIST GENERAL LIMITATION #7, (SEE |
| | PAGE 17) WHICH REQUIRES RAS 117 CALCULATIONS BY EITHER |
| | A ENGINEER OR ARCHITECT. |
| | 014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED |
| | BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL |
| | ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING |
| | SYSTEM, MATERIALS, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT |
| | EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE |
| | WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE |
| | OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE |
| | SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| | DOCUMENTS. |
| | |