| 2016-08-16 11:38:22 | ) BUILDING PROVISO: |
| | SHELL PERMIT : 13060228 |
| | 8146 OKEECHOBEE BLVD. |
| | MEMO: FROM KUOPPALA & ASSOC. |
| | DATED: 05/14/15 |
| | BUILD: 5& 6 |
| | ADDENDUM A ITEM # 1. DELETE ALL CONCRETE FLOOR SLABS, |
| | SHALL BE POURED WITH INTERIOR BUILD OUT. |
| | FLOOD ZONE CERTIFICATES, 2014 FBC BUILDING 1612 AND |
| | CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| | STRUCTURE IS LOCATED IN AN "AH" FLOOD ZONE. A FLOOD |
| | ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW |
| | CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN |
| | ADDITIONAL 6 INCHES OF ELEVATION. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. COMPLETED WITH PLAN REVIEW FOR SHELL BUILDING. |
| | |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED. |
| | |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS |
| | FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| | OMB NO. 1660-0008 |
| | EXPIRATION DATE: NOV. 30/2018 |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |