| Notes |
| Date |
Text |
| 2016-06-13 17:30:21 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16060592 | | | 6/13/16 | | | | | | 1) SHEET M-1: FIRE DAMPERS MISSING AT DUCT DROPS | | | THROUGH RATED CORRIDOR CEILINGS. | | | | | | 2) M-1: PROVIDE A RETURN AIR GRILL SYMBOL FOR RTU-1. | | | | | | 3) M-1: EXHAUST FANS EF-4 & EF-5 ARE UNDERSIZED IN | | | CAPACITIES PER TABLE 403.3 FOOTNOTE E. | | | | | | 4) M-1 & M-2: PROVIDE AN EXHAUST AIR CALCULATION FOR | | | EF-6 IN THE STAFF LOUNGE. | | | | | | 5) M-1: PROVIDE NOTE #7 AT RTU'S 8,9,10, & 11. | | | | | | 6) M-1: CORRECT NOTE #17 INDICATING 3/4" CONDENSATE | | | PIPING- THE PLAN INDICATES 2" | | | | | | 7) M-1: PROVIDE O/A DAMPERS WITH AUTOMATIC CONTROL FOR | | | THE RTU'S- SECTION C403.2.4.4 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 8) M-1: PROVIDE A FL. PRODUCT APPROVAL OR MIAMI-DADE | | | NOA FOR THE EXHAUST OUTLET LOUVERS- SEE NOTE #12 | | | | | | 9) M-1: PROVIDE NOTE #15 AT FLEX DUCT PENETRATING THE | | | RATED OFFICE #5 WALL, AND A DETAIL SHOWING HOW THE | | | ACCESS TO THE DAMPER WILL BE PROVIDED | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|