2016-06-13 17:30:211ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16060592
 6/13/16
  
 1) SHEET M-1: FIRE DAMPERS MISSING AT DUCT DROPS
 THROUGH RATED CORRIDOR CEILINGS.
  
 2) M-1: PROVIDE A RETURN AIR GRILL SYMBOL FOR RTU-1.
  
 3) M-1: EXHAUST FANS EF-4 & EF-5 ARE UNDERSIZED IN
 CAPACITIES PER TABLE 403.3 FOOTNOTE E.
  
 4) M-1 & M-2: PROVIDE AN EXHAUST AIR CALCULATION FOR
 EF-6 IN THE STAFF LOUNGE.
  
 5) M-1: PROVIDE NOTE #7 AT RTU'S 8,9,10, & 11.
  
 6) M-1: CORRECT NOTE #17 INDICATING 3/4" CONDENSATE
 PIPING- THE PLAN INDICATES 2"
  
 7) M-1: PROVIDE O/A DAMPERS WITH AUTOMATIC CONTROL FOR
 THE RTU'S- SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  
 8) M-1: PROVIDE A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE EXHAUST OUTLET LOUVERS- SEE NOTE #12
  
 9) M-1: PROVIDE NOTE #15 AT FLEX DUCT PENETRATING THE
 RATED OFFICE #5 WALL, AND A DETAIL SHOWING HOW THE
 ACCESS TO THE DAMPER WILL BE PROVIDED
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719