Date Text
2016-06-15 15:46:488146 OKEECHOBEE BOULEVARD
 PERMIT #16060592
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COVER SHEET AND SHEET SP-1 INDICATES FLOOR AREAS OF
 11,900 SQ.FT. AND 1,440 SQ.FT. SEPARATED WITH A 4-HOUR
 CMU WALL (FIRE WALL?), HOWEVER, UTILITIES AND EGRESS
 ARE SHARED BETWEEN THE TWO SPACES. EDUCATIONAL
 OCCUPANCY BUILDINGS 12,000 SQ.FT. SHALL BE PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 SHEET LS-1: DISTANCE BETWEEN EXIT SIGNS IN CORRIDOR
 EXCEEDS 100 FEET. PER NFPA 101-7.10.1.5.2 NEW SIGN
 PLACEMENT SHALL BE SUCH THAT NO POINT IN AN EXIT ACCESS
 CORRIDOR IS IN EXCESS OF THE RATED VIEWING DISTANCE OR
 100 FEET, WHICHEVER IS LESS, FROM THE NEAREST SIGN.
  
 COULD NOT LOCATE ANY DOOR PANIC HARDWARE. PER NFPA
 101-14.2.2.2.2 ANY DOOR IN A REQUIRED MEANS OF EGRESS
 FROM AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH
 OR LOCK ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE.
  
 PER NFPA 1-8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE
 AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE A TRAFFIC SITE PLAN INDICATING FIRE LANES, FIRE
 HYDRANTS AND VEHICLE STACKING LOCATION (CHILD
 DROP-OFF/PICK UP). NOTE FIRE LANES ARE REQUIRED TO BE
 20 FEET IN CLEAR, UNOBSTRUCTED (NO PARKING/WAITING)
 WIDTH.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  