| 2016-06-15 15:46:48 | 8146 OKEECHOBEE BOULEVARD |
| | PERMIT #16060592 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | COVER SHEET AND SHEET SP-1 INDICATES FLOOR AREAS OF |
| | 11,900 SQ.FT. AND 1,440 SQ.FT. SEPARATED WITH A 4-HOUR |
| | CMU WALL (FIRE WALL?), HOWEVER, UTILITIES AND EGRESS |
| | ARE SHARED BETWEEN THE TWO SPACES. EDUCATIONAL |
| | OCCUPANCY BUILDINGS 12,000 SQ.FT. SHALL BE PROTECTED |
| | THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM. |
| | |
| | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE |
| | REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE |
| | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN |
| | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA |
| | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | SHEET LS-1: DISTANCE BETWEEN EXIT SIGNS IN CORRIDOR |
| | EXCEEDS 100 FEET. PER NFPA 101-7.10.1.5.2 NEW SIGN |
| | PLACEMENT SHALL BE SUCH THAT NO POINT IN AN EXIT ACCESS |
| | CORRIDOR IS IN EXCESS OF THE RATED VIEWING DISTANCE OR |
| | 100 FEET, WHICHEVER IS LESS, FROM THE NEAREST SIGN. |
| | |
| | COULD NOT LOCATE ANY DOOR PANIC HARDWARE. PER NFPA |
| | 101-14.2.2.2.2 ANY DOOR IN A REQUIRED MEANS OF EGRESS |
| | FROM AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE |
| | PERSONS SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH |
| | OR LOCK ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR |
| | FIRE EXIT HARDWARE. |
| | |
| | PER NFPA 1-8.3.2.4, EACH FIRE BARRIER SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE |
| | AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| | CENTER. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | PROVIDE A TRAFFIC SITE PLAN INDICATING FIRE LANES, FIRE |
| | HYDRANTS AND VEHICLE STACKING LOCATION (CHILD |
| | DROP-OFF/PICK UP). NOTE FIRE LANES ARE REQUIRED TO BE |
| | 20 FEET IN CLEAR, UNOBSTRUCTED (NO PARKING/WAITING) |
| | WIDTH. |
| | |