| 2016-06-16 14:59:28 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL | | | LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE | | | ALARM, ACCESS CONTROLS (GATES), CCTV, PHONE AND DATA, | | | WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE. | | | 2. ELECTRICAL NOTES, PLEASE REVISE TYPO TO INDICATE NEC | | | 2011 NOT 2012 AS SHOWN. | | | 3. PLEASE LABEL THE RECEPTACLE OUTLET IN STAFF LOUNGE | | | AREA WITHIN 6FT OF SINK TO BE GFCI PROTECTED. SEE REF | | | OUTLET. NEC 210.8B5 | | | 4. LABEL GFCI ALL RECEPTACLES FOR THE DRINKING FOUNTAIN | | | SHOWN ON CIRCUIT B2 THRU B10 PER NEC 422.52 | | | 5. PROVIDE PHOTOMETRIC FOR EXTERIOR AND INTERIOR AREAS. | | | FBC 107.3.5 AND FBC SECTION 468 .3.7 LIGHTING | | | REQUIREMENTS | | | 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | | THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|