2016-06-16 14:59:28INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS (GATES), CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. ELECTRICAL NOTES, PLEASE REVISE TYPO TO INDICATE NEC
 2011 NOT 2012 AS SHOWN.
 3. PLEASE LABEL THE RECEPTACLE OUTLET IN STAFF LOUNGE
 AREA WITHIN 6FT OF SINK TO BE GFCI PROTECTED. SEE REF
 OUTLET. NEC 210.8B5
 4. LABEL GFCI ALL RECEPTACLES FOR THE DRINKING FOUNTAIN
 SHOWN ON CIRCUIT B2 THRU B10 PER NEC 422.52
 5. PROVIDE PHOTOMETRIC FOR EXTERIOR AND INTERIOR AREAS.
 FBC 107.3.5 AND FBC SECTION 468 .3.7 LIGHTING
 REQUIREMENTS
 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  