| Plan Review Notes For Permit 16060591 |
| Permit Number |
16060591 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-15 16:44:06 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING | | | PERMIT #16060591 | | | 6/15/16 | | | | | | 1) SHEET M-1.01: PLEASE CLARIFY IF THE SEPARATION WALL | | | IN DETAIL A IS FIRE-RATED- FIRE DAMPERS ARE REQUIRED | | | FOR THE RETURN AIR PLENUM GRILL AND SUPPLY DUCT IF THE | | | WALL IS RATED. | | | | | | 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|