| Plan Review Notes For Permit 16060502 |
| Permit Number |
16060502 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-22 15:32:19 | 1ST REVIEW | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | | | | PLUMBING COMMENTS: | | | | | | | | | 1. A SEPARATE PERMIT IS REQUIRED FOR BOILER | | | INSTALLATION. PER WPB AMEND.TO FBC 105.1 | | | | | | 2. PROVIDE INSTILLATION GUIDE FOR VENTING ON BOILERS. | | | PER WPB AMEND.TO FBC 107.2.1 | | | | | | 3. PROVIDE BTU LOAD OF EXISTING BOILERS . PER WPB | | | AMEND.TO FBC 107.2.1 | | | | | | 4.IF NEW BOILER BTU LOAD IS LARGER THAN EXISTING | | | PROVIDE EXISTING GAS PIPE SIZES, LENGTH AND PRESSURE. | | | PER WPB AMEND.TO FBC 107.2.1 |
|