| Plan Review Notes For Permit 16060502 |
| Permit Number |
16060502 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-15 10:56:44 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16060502 | | | 6/15/16 | | | | | | 1) SHEET M1.1: PROVIDE THE EFFICIENCY RATINGS OF THE | | | RTU'S IN THE SCHEDULE PER TABLE C403.2.3(1) FBC-14 | | | ENERGY CONSERVATION. | | | | | | 2) M1.1: PROVIDE THE SCOP OF THE DATAAIRE AC SYSTEM IN | | | THE IT ROOM- TABLE C403.2.3(10). | | | | | | 3) M2.1: THE PLAN DOES NOT SHOW THE OPERATIONS | | | MANAGER'S ROOM S-116A. | | | | | | 4) M3.1: PROVIDE A COMBUSTION AIR CALCULATION FOR THE | | | BOILER ROOMS AND MORE SPECIFIC INFORMATION ABOUT THE | | | SIDEWALL VENTS INCLUDING- TYPE AND SIZE, AND EXACT | | | LOCATIONS SHOWN WITH DIMENSIONS FROM FLOOR AND CEILING- | | | SEE SECTION 304 FBC-14 FUEL GAS. | | | | | | 5) M3.1: CLARIFY NOTE #8 AND SHOW THE VENT PIPE RUN AND | | | TERMINATION LOCATION. SUBMIT MANUFACTURER'S | | | SPECIFICATIONS FOR THE BOILERS AND VENTING SYSTEMS. | | | | | | 6) M4.1: PROVIDE THE WIND LOAD DESIGN CRITERIA ON THE | | | PLAN INCLUDING WIND SPEED, IMPORTANCE FACTOR, RISK | | | CATEGORY, AND EXPOSURE- SEE SECTION 301.15 FBC-14 | | | MECHANICAL, AND SECTION 1609 FBC-14 BUILDING. | | | | | | 7) M4.1: PROVIDE A DETAIL FOR ANCHORING THE CU-1 TO THE | | | EXISTING STAND. | | | | | | 8) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR | | | SYSTEMS OF RTU'S 3-9 PER SECTION 606.2.1. PLEASE | | | PROVIDE NOTES AND DETAILS ON TH PLAN VERIFYING | | | COMPLIANCE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|