Plan Review Notes
Plan Review Notes For Permit 16060502
Permit Number 16060502
Review Stop M
Sequence Number 1
Notes
Date Text
2016-06-15 10:56:441ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16060502
 6/15/16
  
 1) SHEET M1.1: PROVIDE THE EFFICIENCY RATINGS OF THE
 RTU'S IN THE SCHEDULE PER TABLE C403.2.3(1) FBC-14
 ENERGY CONSERVATION.
  
 2) M1.1: PROVIDE THE SCOP OF THE DATAAIRE AC SYSTEM IN
 THE IT ROOM- TABLE C403.2.3(10).
  
 3) M2.1: THE PLAN DOES NOT SHOW THE OPERATIONS
 MANAGER'S ROOM S-116A.
  
 4) M3.1: PROVIDE A COMBUSTION AIR CALCULATION FOR THE
 BOILER ROOMS AND MORE SPECIFIC INFORMATION ABOUT THE
 SIDEWALL VENTS INCLUDING- TYPE AND SIZE, AND EXACT
 LOCATIONS SHOWN WITH DIMENSIONS FROM FLOOR AND CEILING-
 SEE SECTION 304 FBC-14 FUEL GAS.
  
 5) M3.1: CLARIFY NOTE #8 AND SHOW THE VENT PIPE RUN AND
 TERMINATION LOCATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE BOILERS AND VENTING SYSTEMS.
  
 6) M4.1: PROVIDE THE WIND LOAD DESIGN CRITERIA ON THE
 PLAN INCLUDING WIND SPEED, IMPORTANCE FACTOR, RISK
 CATEGORY, AND EXPOSURE- SEE SECTION 301.15 FBC-14
 MECHANICAL, AND SECTION 1609 FBC-14 BUILDING.
  
 7) M4.1: PROVIDE A DETAIL FOR ANCHORING THE CU-1 TO THE
 EXISTING STAND.
  
 8) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF RTU'S 3-9 PER SECTION 606.2.1. PLEASE
 PROVIDE NOTES AND DETAILS ON TH PLAN VERIFYING
 COMPLIANCE.
  