| Plan Review Notes For Permit 16060502 |
| Permit Number |
16060502 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-27 15:35:09 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET M 5.2 - DOES THIS SHEET INDICATE DUCT | | | DETECTORS FOR EACH UNIT OR JSUT THOSE REQUIRED BY CODE? | | | | | | DUCT DETECTORS | | | PER NFPA 90 A , CHAPTER 6 CONTROLS | | | 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL. | | | 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE | | | TESTED AT LEAST ANNUALLY. | | | 6.4.2* LOCATION. | | | 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR | | | DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS: | | | (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY | | | BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A | | | CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN) | | | (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON | | | RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR | | | INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A | | | CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND | | | SERVING MORE THAN ONE STORY | | | | | | 2) SHEET M 5.2 & E 2.2 - THERE ARE REFERENCES TO | | | CONNECTIONS TO THE FIRE ALARM PANELS. ALL WORK ON THE | | | FIRE ALARM SYSTEM SHALL BE SUBMITTED, INSTALLED, AND | | | TESTED BY CERTIFIED LIFE SAFETY CONTRACTORS UNDER | | | SEPARATE SHOP DRAWINGS. | | | | | | PLEASE PROVIDE AN INDICATING NOTE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|