Plan Review Notes
Plan Review Notes For Permit 16060502
Permit Number 16060502
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-06-27 15:35:09THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET M 5.2 - DOES THIS SHEET INDICATE DUCT
 DETECTORS FOR EACH UNIT OR JSUT THOSE REQUIRED BY CODE?
  
 DUCT DETECTORS
 PER NFPA 90 A , CHAPTER 6 CONTROLS
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
 2) SHEET M 5.2 & E 2.2 - THERE ARE REFERENCES TO
 CONNECTIONS TO THE FIRE ALARM PANELS. ALL WORK ON THE
 FIRE ALARM SYSTEM SHALL BE SUBMITTED, INSTALLED, AND
 TESTED BY CERTIFIED LIFE SAFETY CONTRACTORS UNDER
 SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE AN INDICATING NOTE.
  
 PETER LEDUC
 FIRE MARSHAL