| Plan Review Notes For Permit 16060298 |
| Permit Number |
16060298 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-27 18:04:09 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | - FBC 107.2.1 CLEARLRY DEFINE SCOPE OF WORK ? | | | ALTERATION 1 OR 2 ? PROVIDE A FLOOR PLAN WITH | | | ELECTRICAL INFORMATION. | | | | | | - IF WORK IN THE KITCHEN AND BATHROOMS IS BEING | | | CONDUCTED THE FOLLOWING ARE THE MINIMUM REQUIREMENTS | | | E3901.3 | | | | | | SMALL APPLIANCE RECEPTACLES, E3901.6 BATHROOM, | | | E3901.2.4 COUNTERTOP RECEPTACLES, E3902.1 BATHROOM | | | RECEPTACLES | | | | | | E3902.6 KITCHEN RECEPTACLES. | | 2016-06-27 16:19:48 | NO ELECTRICAL SHOWN |
|