| Plan Review Notes For Permit 16060288 |
| Permit Number |
16060288 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-08 06:19:45 | 1) SHT.P300 - CLARIFY THE TOTAL BTU LOAD FOR THE GAS | | | SYSTEM. WHAT IS 115E0? I CALCULATE 1,118,000 BTU'S. | | | PLACE THIS ON THE PLANS. | | | 2) THE GAS PLAN REFERENCES TABLE 402.1 (1 ) OF THE FUEL | | | GAS CODE. THERE IS NO SUCH TABLE IN THE GAS CODE. PLACE | | | THE CORRECT TABLE NUMBER ON THE PLANS. | | | 3) SHOW THE CORRESPONDING EHD NUMBER OF THE CORRUGATED | | | STAINLESS STEEL TUBING NEXT TO THE TUBING SIZE ON THE | | | PLANS FOR EACH PIPE SIZE SHOWN. WPB AMENDMENTS TO FBC | | | SEC.107.2.1. | | | 4) THE PLAN SHOWS A 1 INCH GALVANIZED LINE SUPPLYING 2 | | | TANKLESS WATER HEATERS AND THE POOL HEATER. THIS LINE | | | IS SEVERELY UNDERSIZED IF THIS IS LESS THAN A 2 PSI | | | SYSTEM. SUBMIT THE NUMBER OF THE CORRECT SIZING TABLE | | | AND PSI OF THE SYSTEM FOR THE GALVANIZED PIPE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|