2017-08-18 17:14:44PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A-5 THE TIE BEAM SCHEDULE SPECIFIES
 STIRRUPS AT 48" O.C. FOR THE NEW 8" X 16" CONCRETE BEAM
 SPANNING THE 13' 10" OPENING. THERE WILL ONLY BE 4
 STIRRUPS ON THE BEAM AT THIS SPACING. THERE WILL ONLY
 BE ONE STIRRUP NEAR THE COLUMNS AT THE ENDS OF THE BEAM
 WHERE THE SHEAR FORCES WOULD OCCUR. REDUCE THE SPACING
 OF THE STIRRUPS FOR THE BEAM SO THAT THERE WILL BE AN
 ADEQUATE NUMBER OF STIRRUPS NEAR THE ENDS OF THE BEAM
 OR PROVIDE STRUCTURAL CALCULATIONS TO SHOW THAT 48" OC
 SPACING IS ADEQUATE. FBC 107.2.1.3
  
 2) DETAIL 5 ON A-5 IS TITLED STEEL BUCKET DETAIL AND
 HAS BEEN REDESIGNED WITHOUT STEEL BUCKETS. PLEASE
 REVISE. FBC 107.2
  
 3) DETAIL 5 ON A-5 STATES THAT THE FOUR VERTICAL #6
 REBARS ARE TO BE CONTINUOUS TO THE FOOTING. SHOW ON THE
 PLANS HOW THEY WILL BE TIED INTO THE EXISTING FOOTING
 OR INTO NEW FOOTERS IF NEW ONES ARE TO BE INSTALLED.
 FBC 107.2.1.3
  
 4) PROVIDE A REBAR PLACEMENT DETAIL THAT SHOWS HOW THE
 COLUMN STEEL AND BEAM STEEL WILL BE LAPPED. SHOW
 WHETHER THE BEAM REBAR WILL BE TIED INTO THE EXISTING
 TIE BEAM STEEL, IF IT BE DOWELED INTO THE EXISTING TIE
 BEAM, TURNED DOWN INTO THE NEW COLUMNS OR SOME
 COMBINATION OF THESE. FBC 107.2.1.3
  
  
  
  
  
  