2016-07-07 11:45:18INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE UPDATE ALL CODE REFERENCES TO REFLECT ABOVE
 STATED STANDARDS.
 2. LABEL NEW RECEPTACLE AT PENINSULA TO GFCI PROTECTED
 AND PLACE A GENERAL NOTE FOR KITCHEN TO COMPLY WITH
 REQUIRED SPACING PER FBC RES E3901.2.4 E3902.6
 3. SHOW AND PROVIDE A COMPLETE ELECTRICAL LOAD
 CALCULATION, NOT PARTIAL AS SHOWN. FBC 107.3.5
 4. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
  