| Plan Review Notes For Permit 16060280 |
| Permit Number |
16060280 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-07 11:45:18 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE UPDATE ALL CODE REFERENCES TO REFLECT ABOVE | | | STATED STANDARDS. | | | 2. LABEL NEW RECEPTACLE AT PENINSULA TO GFCI PROTECTED | | | AND PLACE A GENERAL NOTE FOR KITCHEN TO COMPLY WITH | | | REQUIRED SPACING PER FBC RES E3901.2.4 E3902.6 | | | 3. SHOW AND PROVIDE A COMPLETE ELECTRICAL LOAD | | | CALCULATION, NOT PARTIAL AS SHOWN. FBC 107.3.5 | | | 4. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | |
|