2016-08-19 15:24:12RESIDENTIAL (R3) REVISION, FIFTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT
 THE STAIR HALL. PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL COVER PAGES AND THE CORRESPONDING DRAWINGS.
  
 RESPONSE:
 FLORIDA PRODUCT APPROVAL FL16708-R4 SUBMITTED WAS
 MARKED WITH SELECTED DOOR FL16708.1. THE DESIGN
 PRESSURES FOR THIS DOOR ARE +/-50PSF FOR A 3'-0" X
 8'-0" DOOR. THE DESIGN PRESSURES DON'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT ON SHEET A4. NEED
 TO PROVIDE PRODUCT APPROVAL FOR SPECIFIED INSWING ENTRY
 DOOR SIZE THAT MEETS THE CALCULATED DESIGN PRESSURES.
  
 2- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT APPROVAL
 PRIOR TO SUBMITTAL.
  