| 2016-08-08 09:37:23 | RESIDENTIAL (R3) REVISION ADDRESSING BUILDING PROVISO, |
| | FOURTH BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 08/08/16 MET WITH DON STARR TO GO OVER RE- SUBMITTAL. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: |
| | A) FLAT ROOF . AND, IDENTIFY APPROVED ASSEMBLY TO BE |
| | INSTALLED. NOTE: SIGNED & SEALED RAS 117 CALCULATIONS |
| | WILL BE REQUIRED IF THE ASSEMBLY DOESN'T MEET THE |
| | DESIGN PRESSURES OF SEC. R301. |
| | |
| | NOTE: KEEP IN MIND THAT THERE ARE TWO DIFFERENT |
| | APPLICATIONS. THERE IS A FLAT ROOF ASSEMBLY OVER THE |
| | ENTRY TOWER AND THERE IS ANOTHER FLAT ROOF FOR THE |
| | SECOND FLOOR DECK. THE SECOND FLOOR DECK ASSEMBLY |
| | REQUIRES A SYSTEM THAT IS DESIGNED TO RECEIVE TILE. |
| | |
| | RESPONSE: |
| | ENGINEERED RAS 117 CALCULATIONS SUBMITTED REFERENCE |
| | FLORIDA PRODUCT APPROVAL FL2144-R5 SYSTEM W-1. FLORIDA |
| | PRODUCT APPROVAL FL 2144-R5 WAS REVISED WITH REVISION |
| | #6. THE CURRENT FLORIDA PRODUCT APPROVAL IS FL2144-R6. |
| | THE CURRENT FLORIDA PRODUCT APPROVAL DOESN'T HAVE |
| | ASSEMBLY W-1. REVISE CALCULATIONS AS REQUIRED TO MATCH |
| | CURRENT PRODUCT APPROVAL. |
| | THERE IS ANOTHER PRODUCT APPROVAL SUBMITTED. THIS ONE |
| | IS A MIAMI-DADE NOA. THIS MIAMI-DADE NOA IS FOR |
| | INSULATED ASSEMBLIES ONLY. SELECT INSULATED ASSEMBLY TO |
| | BE INSTALLED AND PROVIDE RAS 117 CALCULATIONS |
| | ACCORDINGLY. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | B) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED |
| | TILE AS SPECIFIED ON PLANS. AND, IDENTIFY APPROVED |
| | ASSEMBLY TO BE INSTALLED. NOTE: SIGNED & SEALED RAS 117 |
| | CALCULATIONS WILL BE REQUIRED IF THE ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES OF SEC. R301. |
| | SEAL-O-FLEX NOA 15-0406.03 SUBMITTED IS FOR INSULATED |
| | ASSEMBLIES. ARCHITECTURAL PLANS DON'T SPECIFY INSULATED |
| | ASSEMBLIES. |
| | |
| | RESPONSE: |
| | SELECT INSULATED ASSEMBLY TO BE INSTALLED AND PROVIDE |
| | RAS 117 CALCULATIONS ACCORDINGLY. |
| | |
| | |
| | |
| | ORIGINAL COMMENT: |
| | C) INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT |
| | THE STAIR HALL. PROVIDE COMPLETE FLORIDA PRODUCT |
| | APPROVAL COVER PAGES AND THE CORRESPONDING DRAWINGS. |
| | |
| | RESPONSE: MIAMI-DADE NOA SUBMITTED EXPIRED IN 2012 AND |
| | IS NOT PART OF THE FLORIDA PRODUCT APPROVAL SUBMITTED. |
| | IF THERE IS NO CURRENT FLORIDA PRODUCT APPROVAL, THEN |
| | MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL. |
| | ADVICE IF LOCAL PRODUCT APPROVAL IS REQUESTED FOR |
| | FURTHER INFORMATION REGARDING SUBMITTAL PROCESS. |
| | |
| | 2- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT |
| | APPROVALS. |
| | |
| | |