Plan Review Notes
Plan Review Notes For Permit 16060273
Permit Number 16060273
Review Stop B
Sequence Number 3
Notes
Date Text
2016-07-25 17:04:12RESIDENTIAL (R3) REVISION ADDRESSING BUILDING PROVISO,
 THIRD BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) FLAT ROOF. AND, IDENTIFY APPROVED ASSEMBLY TO BE
 INSTALLED. NOTE: SIGNED & SEALED RAS 117 CALCULATIONS
 WILL BE REQUIRED IF THE ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES OF SEC. R301.
  
 RESPONSE:
 (1) THE DESIGN PRESSURES SHOWN ON SHEET A-4 ARE TOO LOW
 FOR THE FLAT ROOF . SEE TABLE R301.2(2) OF
 FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE DESIGN
 PRESSURES ACCORDING TO HEIGHT AND BUILDING EXPOSURE.
  
 (2) SELECTED ASSEMBLY FROM FLORIDA PRODUCT APPROVAL
 FL2144-R6 CAN NOT BE USED BECAUSE IT DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES, INCLUDING CORNER
 ZONES (ROOF ZONE #3). THE MAXIMUM DESIGN PRESSURES OF
 THE ASSEMBLIES WITH ADHERED MEMBRANES CAN NOT BE
 EXTRAPOLATED. SEE LIMITATION #9. THE MAXIMUM DESIGN
 PRESSURES FOR ASSEMBLY W-A-2 ARE -85PSF. THE DESIGN
 PRESSURES FOR ROOF ZONE #3 ARE HIGHER. THEREFORE, IT
 CAN NOT BE USED. NOTE: COORDINATE DESIGN PRESSURES WITH
 ITEM #(1) ABOVE.
  
  
  
 ORIGINAL COMMENT:
 B) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED
 TILE AS SPECIFIED ON PLANS. AND, IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. NOTE: SIGNED & SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED IF THE ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES OF SEC. R301.
 SEAL-O-FLEX NOA 15-0406.03 SUBMITTED IS FOR INSULATED
 ASSEMBLIES. ARCHITECTURAL PLANS DON'T SPECIFY INSULATED
 ASSEMBLIES.
  
 RESPONSE: REPEAT COMMENT. (1) FLORIDA PRODUCT APPROVAL
 FL2144-R6 SUBMITTED CAN NOT BE USED. IT'S NOT DESIGNED
 TO RECEIVE TILE AS SPECIFIED ON PLANS. NOTE: REVISE
 DESIGN PRESSURES SHOWN ON THE FLAT ROOF UPLIFT DIAGRAM
 AND DETAIL #2 ON SHEET A-4 SUBMITTED.
  
  
 ORIGINAL COMMENT:
 C) INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT
 THE STAIR HALL. PROVIDE COMPLETE FLORIDA PRODUCT
 APPROVAL COVER PAGES AND THE CORRESPONDING DRAWINGS.
  
 RESPONSE: NEED THE FLORIDA PRODUCT APPROVAL COVER PAGE
 THAT CORRESPONDS TO DRAWINGS SUBMITTED. IF THERE IS NO
 CURRENT FLORIDA PRODUCT APPROVAL, THEN MANUFACTURER MAY
 APPLY FOR LOCAL PRODUCT APPROVAL. ADVICE IF LOCAL
 PRODUCT APPROVAL IS REQUESTED FOR FURTHER INFORMATION
 REGARDING SUBMITTAL PROCESS.
  
 2- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved