| Date |
Text |
| 2016-07-25 17:04:12 | RESIDENTIAL (R3) REVISION ADDRESSING BUILDING PROVISO, |
| | THIRD BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: |
| | A) FLAT ROOF. AND, IDENTIFY APPROVED ASSEMBLY TO BE |
| | INSTALLED. NOTE: SIGNED & SEALED RAS 117 CALCULATIONS |
| | WILL BE REQUIRED IF THE ASSEMBLY DOESN'T MEET THE |
| | DESIGN PRESSURES OF SEC. R301. |
| | |
| | RESPONSE: |
| | (1) THE DESIGN PRESSURES SHOWN ON SHEET A-4 ARE TOO LOW |
| | FOR THE FLAT ROOF . SEE TABLE R301.2(2) OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE DESIGN |
| | PRESSURES ACCORDING TO HEIGHT AND BUILDING EXPOSURE. |
| | |
| | (2) SELECTED ASSEMBLY FROM FLORIDA PRODUCT APPROVAL |
| | FL2144-R6 CAN NOT BE USED BECAUSE IT DOESN'T MEET THE |
| | DESIGN PRESSURES FOR ALL ROOF ZONES, INCLUDING CORNER |
| | ZONES (ROOF ZONE #3). THE MAXIMUM DESIGN PRESSURES OF |
| | THE ASSEMBLIES WITH ADHERED MEMBRANES CAN NOT BE |
| | EXTRAPOLATED. SEE LIMITATION #9. THE MAXIMUM DESIGN |
| | PRESSURES FOR ASSEMBLY W-A-2 ARE -85PSF. THE DESIGN |
| | PRESSURES FOR ROOF ZONE #3 ARE HIGHER. THEREFORE, IT |
| | CAN NOT BE USED. NOTE: COORDINATE DESIGN PRESSURES WITH |
| | ITEM #(1) ABOVE. |
| | |
| | |
| | |
| | ORIGINAL COMMENT: |
| | B) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED |
| | TILE AS SPECIFIED ON PLANS. AND, IDENTIFY APPROVED |
| | ASSEMBLY TO BE INSTALLED. NOTE: SIGNED & SEALED RAS 117 |
| | CALCULATIONS WILL BE REQUIRED IF THE ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES OF SEC. R301. |
| | SEAL-O-FLEX NOA 15-0406.03 SUBMITTED IS FOR INSULATED |
| | ASSEMBLIES. ARCHITECTURAL PLANS DON'T SPECIFY INSULATED |
| | ASSEMBLIES. |
| | |
| | RESPONSE: REPEAT COMMENT. (1) FLORIDA PRODUCT APPROVAL |
| | FL2144-R6 SUBMITTED CAN NOT BE USED. IT'S NOT DESIGNED |
| | TO RECEIVE TILE AS SPECIFIED ON PLANS. NOTE: REVISE |
| | DESIGN PRESSURES SHOWN ON THE FLAT ROOF UPLIFT DIAGRAM |
| | AND DETAIL #2 ON SHEET A-4 SUBMITTED. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | C) INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT |
| | THE STAIR HALL. PROVIDE COMPLETE FLORIDA PRODUCT |
| | APPROVAL COVER PAGES AND THE CORRESPONDING DRAWINGS. |
| | |
| | RESPONSE: NEED THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| | THAT CORRESPONDS TO DRAWINGS SUBMITTED. IF THERE IS NO |
| | CURRENT FLORIDA PRODUCT APPROVAL, THEN MANUFACTURER MAY |
| | APPLY FOR LOCAL PRODUCT APPROVAL. ADVICE IF LOCAL |
| | PRODUCT APPROVAL IS REQUESTED FOR FURTHER INFORMATION |
| | REGARDING SUBMITTAL PROCESS. |
| | |
| | 2- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT |
| | APPROVALS. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |