| 2016-06-14 14:18:14 | 06/14/16: PER MEETING WITH STEVE MALLEK (ROOFING |
| | CONTRACTOR), THE ROOFING SUB-PERMIT WAS ISSUED TO ALLOW |
| | FOR CONCRETE ROOF TILE DRY-IN INSPECTION . FOLLOWING |
| | COMMENTS NEED TO BE ADDRESSED BEFORE INSPECTIONS TO |
| | AVOID CONFLICTS/DELAYS. THIS CHECKLIST WAS E-MAILED TO |
| | GENERAL CONTRACTOR AND ROOFING CONTRACTOR. JG. |
| | |
| | |
| | RESIDENTIAL (R3) REVISION ADDRESSING BUILDING PROVISO, |
| | SECOND BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: |
| | A) FLAT ROOF. AND, IDENTIFY APPROVED ASSEMBLY TO BE |
| | INSTALLED. NOTE: SIGNED & SEALED RAS 117 CALCULATIONS |
| | WILL BE REQUIRED IF THE ASSEMBLY DOESN'T MEET THE |
| | DESIGN PRESSURES OF SEC. R301. |
| | |
| | RESPONSE: NOT ADDRESSED YET. NEED TO PROVIDE. THIS IS |
| | FOR THE FLAT DECK ABOVE THE NEW TWO STORY STAIRWAY |
| | TOWER. SEE PLANS. |
| | |
| | ORIGINAL COMMENT: |
| | B) SECOND FLOOR DECK UNDERLAYMENT DESIGNED TO RECEIVED |
| | TILE AS SPECIFIED ON PLANS. AND, IDENTIFY APPROVED |
| | ASSEMBLY TO BE INSTALLED. NOTE: SIGNED & SEALED RAS 117 |
| | CALCULATIONS WILL BE REQUIRED IF THE ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES OF SEC. R301. |
| | SEAL-O-FLEX NOA 15-0406.03 SUBMITTED IS FOR INSULATED |
| | ASSEMBLIES. ARCHITECTURAL PLANS DON'T SPECIFY INSULATED |
| | ASSEMBLIES. |
| | |
| | RESPONSE: FLORIDA PRODUCT APPROVAL FL2144-R6 SUBMITTED |
| | CAN NOT BE USED BECAUSE OF THE FOLLOWING: (1)IT'S NOT |
| | DESIGNED TO RECEIVED TILE AS SHOWN ON ARCHITECTURAL |
| | PLANS. SEE PRODUCT DESCRIPTION TABLE ON PAGE 1 OF 3 OF |
| | FL2144-R6 SUBMITTED FOR THE ROOF COATINGS ALLOWED FOR |
| | THIS TYPE OF LIQUID APPLIED MEMBRANE. NONE OF THEM |
| | DESCRIBE TILE AS THE ROOF COATING. (2) SELECTED |
| | ASSEMBLIES W-A-1 AND W-A-2 ON PAGE 13 OF 14 OF |
| | FL2144-R6 ARE FOR FULLY ADHERED MEMBRANES WITH MAXIMUM |
| | DESIGN PRESSURES OF -60PSF AND -85PSF RESPECTIVELY. |
| | LIMITATION #9 ON PAGE 3 OF 3 DOESN'T ALLOW DESIGN |
| | PRESSURES AUGMENTATION. ACCORDING TO SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014) THE DESIGN |
| | PRESSURES FOR THE PERIMETER AND CORNER AREAS ARE |
| | HIGHER. THEREFORE THEY CAN NOT BE USED. NEED TO PROVIDE |
| | PRODUCT APPROVAL THAT IS DESIGNED TO RECEIVE TILE AS |
| | SPECIFIED ON PLANS. AND, NEED RAS 117 CALCULATIONS IF |
| | THE SELECTED ASSEMBLY ALLOWS IT. |
| | |
| | ORIGINAL COMMENT: |
| | C) INSWING ENTRY DOOR SIZE DOOR AS SHOWN ON PLANS AT |
| | THE STAIR HALL. PROVIDE COMPLETE FLORIDA PRODUCT |
| | APPROVAL COVER PAGES AND THE CORRESPONDING DRAWINGS. |
| | RESPONSE: NOT ADDRESSED. |
| | |
| | 2- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT |
| | APPROVALS. |
| | |
| | |
| | THE FOLLOWING ARE COMMENTS ARE FOR THE SUBMITTED |
| | INFORMATION: |
| | ORIGINAL COMMENT: |
| | (1) CONCRETE ROOF TILE NOA 12-0222.03 SUBMITTED NOW WAS |
| | ALREADY SUBMITTED AND APPROVED WITH THE ORIGINAL PERMIT |
| | SET. CLARIFY WHY SUBMITTING PRODUCT APPROVAL AGAIN. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | RESPONSE: OK. APPROVED PRODUCT APPROVAL SHOULD BE ON |
| | SITE ALONG WITH THE REST OF THE APPROVED PRODUCT |
| | APPROVALS. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | (2) ARCHITECTURAL PLANS SPECIFY "CEMENT TILE ON 90# |
| | FELT HOT MOPPED ON 30# FELT TIN TAGGED AT 6" EDGES AND |
| | 12" FIELD O.C." THIS SUBMITTAL INCLUDES BORAL TILESEAL |
| | SELF-ADHERING UNDERLAYMENT AND TILE BOND ROOF TILE |
| | ADHESIVE. IF THERE IS A CHANGE IN THE ROOF TILE |
| | FASTENING AND UNDERLAYMENT METHOD, THEN REVISE |
| | ARCHITECTURAL PLANS ACCORDINGLY. SEC. 107.2.1.2 CITY |
| | AMENDMENTS. |
| | RESPONSE: THIS ITEM STILL NEEDS TO BE ADDRESSED. |
| | |
| | (3) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| | CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | NOTE: THERE WAS A ROOFING APPLICATION INSERTED IN THE |
| | PACKAGE SUBMITTED. ROOFING SUB-PERMIT WILL BE PROCESSED |
| | WHEN PENDING ROOFING ITEMS ARE ADDRESSED. |
| | RESPONSE: PER MEETING WITH STEVE MALLEK (CJM ROOFING), |
| | THE ROOFING SUB-PERMIT WAS ISSUED TO ALLOW FOR CONCRETE |
| | TILE DRY-IN INSPECTIONS. ALL THE PENDING ITEMS NEED TO |
| | BE ADDRESSED BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. PLEASE USE THIS REVISION NUMBER |
| | (16060273) FOR SUBMITTAL TO KEEP TRACK OF ALL THE |
| | PENDING ITEMS. |
| | |
| | ***NOTE: |
| | NUMBER OF PAGES WILL BE COORDINATED WHEN ADDRESSING |
| | COMMENTS. NEW PRODUCT APPROVALS (NOT PART OF THE |
| | ORIGINAL PACKAGE) WILL BE ADDED TO THE REVISION FEES. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |