Plan Review Notes
Plan Review Notes For Permit 16060273
Permit Number 16060273
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-18 12:00:53REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO'S
  
 - E3405.2 WORKING CLEARANCES FOR ENERGIZED EQUIPMENT
 AND PANELBOARDS.
 EXCEPT AS OTHERWISE SPECIFIED IN CHAPTERS 34 THROUGH
 43, THE DIMENSION OF THE WORKING SPACE IN THE DIRECTION
 OF ACCESS TO PANELBOARDS AND LIVE PARTS LIKELY TO
 REQUIRE EXAMINATION, ADJUSTMENT, SERVICING OR
 MAINTENANCE WHILE ENERGIZED SHALL BE NOT LESS THAN 36
 INCHES (914 MM) IN DEPTH. DISTANCES SHALL BE MEASURED
 FROM THE ENERGIZED PARTS WHERE SUCH PARTS ARE EXPOSED
 OR FROM THE ENCLOSURE FRONT OR OPENING WHERE SUCH PARTS
 ARE ENCLOSED. IN ADDITION TO THE 36-INCH DIMENSION (914
 MM), THE WORK SPACE SHALL NOT BE LESS THAN 30 INCHES
 (762 MM) WIDE IN FRONT OF THE ELECTRICAL EQUIPMENT AND
 NOT LESS THAN THE WIDTH OF SUCH EQUIPMENT. THE WORK
 SPACE SHALL BE CLEAR AND SHALL EXTEND FROM THE FLOOR OR
 PLATFORM TO A HEIGHT OF 6.5 FEET (1981 MM) OR THE
 HEIGHT OF THE EQUIPMENT, WHICHEVER IS GREATER. IN ALL
 CASES, THE WORK SPACE SHALL ALLOW AT LEAST A 90-DEGREE
 (1.57 RAD) OPENING OF EQUIPMENT DOORS OR HINGED PANELS.
 EQUIPMENT ASSOCIATED WITH THE ELECTRICAL INSTALLATION
 LOCATED ABOVE OR BELOW THE ELECTRICAL EQUIPMENT SHALL
 BE PERMITTED TO EXTEND NOT MORE THAN 6 INCHES (152 MM)
 BEYOND THE FRONT OF THE ELECTRICAL EQUIPMENT.
  
 - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.