2016-06-08 14:17:19ROOF FOR ADDITION, BUILDING REVIEW COMMENTS.
 FBC 2010.
  
 1- THERE IS AN ENGINEER OF RECORD FOR THIS ADDITION.
 ENGINEER OF RECORD NEEDS TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) THE FLAT ROOF PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM
 FLORIDA PRODUCT APPROVAL FL2533-R16 SUBMITTED IS GOING
 TO BE INSTALLED. NEED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES FOR BUILDING EXPOSURE "C" AS SPECIFIED
 BY THE ENGINEER OF RECORD.
 SEC. 1609.1.1 FBC, 5TH EDITION (2014).
  