| Plan Review Notes For Permit 16060269 |
| Permit Number |
16060269 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-07 17:07:21 | RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 5TH EDITION(2014) | | | | | | 1- FLAT ROOF NOA 13-1217.01 SUBMITTED: | | | A) ENGINEER'S CALCULATIONS AND APPROVED ASSEMBLY | | | SUBMITTED DON'T MATCH. ENGINEER SPECIFIES APPROVED | | | SYSTEM E(1) ON PAGE 26 OF 33, WHILE APPROVED ASSEMBLY | | | SUBMITTED IS FOR SYSTEM E(2) ON PAGE 27 OF 33. REVISE | | | AS REQUIRED TO MATCH. IT'S NOT CLEAR WHICH ASSEMBLY IS | | | GOING TO BE INSTALLED. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | B) PROVIDE 2 SIGNED AND SEALED COPIES OF THE ENGINEER'S | | | CALCULATIONS. ONLY ONE WAS SUBMITTED. SEC. 107.1 CITY | | | AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|