| Plan Review Notes For Permit 16060267 |
| Permit Number |
16060267 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-08-29 13:56:27 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PLEASE REVISE LOAD CALCS TO INCLUDE APPLIANCE LOADS | | | AND CORRECT AC HEAT LOADS MATCHING THE PANEL SCHEDULE. | | | NEC 220.82 OPTIONAL ( 2ND REQUEST ) | | | | | | 2] VERIFY RECEPTACLE OUTLET SPACING IN THE | | | MASTER-BEDROOM. NEC 210.52(A) WALL SPACE. |
|