Plan Review Notes
Plan Review Notes For Permit 16060267
Permit Number 16060267
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-21 17:08:31CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) TOTAL CFM FOR AHU #1 EXCEEDS EQUIPMENT SCHEDULE AND
 DESIGNED UNIT AMOUNT.
 (2) BATH EXHAUST IN MASTER BEDROOM BATHROOM ??.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (3) HEAT LOADS CALCULATIONS AND ENERGY CALCULATIONS DO
 NOT MATCH SYSTEM DESIGN ON PLANS. REVIEW AND MAKE
 CORRECTIONS.
 (4) FORM R405-2014 MUST BE SIGNED BY PREPARER AND
 OWNER/AGENT.
  
 JORGE VALIDO
 CITY OF WEST PALM BEACH
 MECHANICAL INSPECTOR/PLANS EXAMINER
 561-805-673
  
  
  
  
  
  
  
  
  
  
  
  
  
  