Plan Review Notes
Plan Review Notes For Permit 16060267
Permit Number 16060267
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-16 16:17:31JOB PERMIT NUMBER: 16060267
 JOB ADDRESS: 710 DUBBINS STREET
 WEST PALM BEACH FLORIDA
 DATE: JUNE 16 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - PANEL SCHEDULE REFLECTS THE FOLLOWING INCORRECT
 INFORMATION. THE A/C COMPRESSOR SHOWS 30 AMP BKR AND
 SPEC SHEET ON AC-1 NAMEPLATE INDICATES ?MAX FUSE SIZE
 60 AMP?. ALL BATHROOM AND SMALL APPLIANCE CIRCUITS MUST
 HAVE A MINIMUM AMPACITY OF 20 AMPS PER NEC
 210.11(C)(1)(3). WATER HEATER IS MISSING BKR SIZE.
 GENERAL RECEPTACLE LOAD ISN?T APPLICABLE FOR LOAD CLACS
 PLEASE SEE NEC 220.82(A)(B)(C) & NEC 220.83 OPTIONAL
 AND EXISTING CALCULATIONS. FBC 107.2.1 INSUFFICIENT
 DOCUMENTS.
 - UNDER THE IMPRESSION THE EXISTING CONDUITS EMT 1 ???
 SINCE NO EQUIPMENT GROUNDING CONDUCTOR IS SHOWN
 ACCORDING TO ANNEX C CONDUIT AND CONDUCTOR FILL TABLE
 2/0 AWG DOESN?T FIT IN THAT RACEWAY ? PLEASE CLARIFY ?
 - LABEL ?GFCI? TO ALL KITCHEN AND PENINSULAR
 COUNTERTOPS OUTLETS NEC 210.8(A). RECEPTACLES LOCATED
 OUTSIDE LABEL ?WR/WP? PER NEC 406.(B).
 - MASTER BATH MISSING RECEPTACLE OUTLET INSTALLED
 WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH BASIN. NEC
 210.52(D)
 - FBC-R 315.1 CARBON MONOXIDE PROTECTION. EVERY
 SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048
 MM) OF EACH ROOM USED FOR SLEEPING PURPOSES.
 - NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE
 DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910
 MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS.
 RELOCATE THE UNITS ACCORDINGLY. ( MASTER BEDROOM )
 - LOW VOLTAGE SHALL BE ON A SEPERATE PERMT. ( IF
 NECCESSARY )
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
  