| 2016-06-16 16:17:31 | JOB PERMIT NUMBER: 16060267 |
| | JOB ADDRESS: 710 DUBBINS STREET |
| | WEST PALM BEACH FLORIDA |
| | DATE: JUNE 16 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - PANEL SCHEDULE REFLECTS THE FOLLOWING INCORRECT |
| | INFORMATION. THE A/C COMPRESSOR SHOWS 30 AMP BKR AND |
| | SPEC SHEET ON AC-1 NAMEPLATE INDICATES ?MAX FUSE SIZE |
| | 60 AMP?. ALL BATHROOM AND SMALL APPLIANCE CIRCUITS MUST |
| | HAVE A MINIMUM AMPACITY OF 20 AMPS PER NEC |
| | 210.11(C)(1)(3). WATER HEATER IS MISSING BKR SIZE. |
| | GENERAL RECEPTACLE LOAD ISN?T APPLICABLE FOR LOAD CLACS |
| | PLEASE SEE NEC 220.82(A)(B)(C) & NEC 220.83 OPTIONAL |
| | AND EXISTING CALCULATIONS. FBC 107.2.1 INSUFFICIENT |
| | DOCUMENTS. |
| | - UNDER THE IMPRESSION THE EXISTING CONDUITS EMT 1 ??? |
| | SINCE NO EQUIPMENT GROUNDING CONDUCTOR IS SHOWN |
| | ACCORDING TO ANNEX C CONDUIT AND CONDUCTOR FILL TABLE |
| | 2/0 AWG DOESN?T FIT IN THAT RACEWAY ? PLEASE CLARIFY ? |
| | - LABEL ?GFCI? TO ALL KITCHEN AND PENINSULAR |
| | COUNTERTOPS OUTLETS NEC 210.8(A). RECEPTACLES LOCATED |
| | OUTSIDE LABEL ?WR/WP? PER NEC 406.(B). |
| | - MASTER BATH MISSING RECEPTACLE OUTLET INSTALLED |
| | WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH BASIN. NEC |
| | 210.52(D) |
| | - FBC-R 315.1 CARBON MONOXIDE PROTECTION. EVERY |
| | SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 |
| | MM) OF EACH ROOM USED FOR SLEEPING PURPOSES. |
| | - NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE |
| | DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910 |
| | MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM |
| | CONTAINING A SHOWER OR TUB UNLESS LISTED FOR |
| | INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS. |
| | RELOCATE THE UNITS ACCORDINGLY. ( MASTER BEDROOM ) |
| | - LOW VOLTAGE SHALL BE ON A SEPERATE PERMT. ( IF |
| | NECCESSARY ) |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | |