| 2016-08-02 12:10:23 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | JOB NAME: |
| | JOB ADDRESS: 501 VILLAGE BLVD. |
| | DESCRIPTION: TENANT IMPROVEMENT |
| | MAST. PERMIT:16020738 |
| | REVISION: 16070202 |
| | |
| | WHILE CONDUCTING THE REVIEW OF THIS REVISION I NOTED |
| | THAT IN ADDITION TO THE PREVIOUSLY MENTIONED FBC-E |
| | LIGHTING CONTROL REQUIREMENTS, I MAY HAVE OVERLOOKED |
| | THE DAYLIGHT ZONE LIGHTING CONTROLS AND THUS ADDRESS |
| | THAT HERE. |
| | SHEET E2.1 |
| | 1. OFFICES 121, 151, 152, 153, ARE MISSING DAYLIGHT |
| | ZONE CONTROL PER FBC-E405.2.0.3 |
| | 2. CONFERENCE ROOMS 124, 125, 126, 154, ARE MISSING |
| | DAYLIGHT ZONE CONTROL AS PER FBC-E405.2.2.3 |
| | 3. VESTIBULE 100 IS MISSING DAYLIGHT ZONE CONTROL AS |
| | PER FBC-E405.2.2.3 |
| | 4. I CAN?T DETERMINE FROM THE FLOOR PLAN IF THE MAIN |
| | WORK AREA 102 WILL HAVE WHAT IS CONSIDERED DAYLIGHT |
| | ZONE, BUT IF SO, IT TOO WILL NEED DAYLIGHT ZONE CONTROL |
| | AS INDICATED ABOVE. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |