| 2016-06-29 09:24:49 | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | 1. SHEET E0.1 UPLOADED TO DRAWINGS FOLDER DOES NOT |
| | MATCH NARRATIVE. CONDUIT SIZES APPEAR AS ON THE |
| | APPROVED PLANS. (FILENET) (NOTE: THERE IS A SHEET E0.1 |
| | UPLOADED TO THE SUPPORTING DOCUMENTS FILE WITH ALL THE |
| | CORRECTIONS TO MATCH THE NARRATIVE, BUT IT IS NOT |
| | SIGNED). CORRECT AS INDICATED. |
| | 2. ELIMINATE ALL THE UNNECESSARY CLOUDING FROM SHEETS |
| | AND LEAVE ONLY THAT WHICH PERTAINS TO THE NARRATIVE. |
| | ALL PRIOR CLOUDING SHOULD BE ON THE CURRENT APPROVED |
| | SET OF PLANS. MAKE INDICATION ON THE NARRATIVE AS TO |
| | WHICH REVISION ADDRESSES THE CHANGES AS NOT ALL |
| | REVISIONS WERE MADE ON THE SAME DATE ON ALL RESPECTIVE |
| | SHEETS. |
| | 3. SHEET E3.2 HAS THE ADDITION OF A CAMERA NOT |
| | ADDRESSED ON THE NARRATIVE IN ADDITION TO THE WORK |
| | MENTIONED FOR THE IT ROOM. CORRECT ACCORDINGLY. |
| | 4. INDICATE COMPLIANCE WITH NEC 760.41(B) FOR CIRCUITS |
| | 20 & 22 OF PANEL THE FIRE ALARM BREAKERS IN PANEL ?L1B? |
| | AT A MINIMUM WITH A NOTE ON THE PLANS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |