Plan Review Notes
Plan Review Notes For Permit 16060194
Permit Number 16060194
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-06 09:07:07INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADDRESS SMOKE DETECTORS IN ALL BEDROOMS AND
 EXTERIOR OF BEDROOMS, SHOW ON PLANS. FBC RES 314
 2. CALCULATIONS NOT ACCURATE PER SCOPE OF WORK SHOWN.
 ADD NEW THANKLESS HEATERS TO LOADS AS SHOWN ON PLANS.
 PROVIDE SPECS FOR NEW HEATERS. FBC 107.3.5
 3. ADDRESS RISER DIAGRAM, SHOW AN INTERSYSTEM BONDING
 CONNECTION, METER CAN AMP RATING, SIZE OF GUTTER BEING
 INSTALLED, AND SHOW EQUIPMENT GROUNDING CONDUCTOR
 FEEDING MLO PANELS. FBC 107.3.5
 4. FURTHER COMMENTS MAY FOLLOW. PLEASE FEEL FREE TO
 CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING THIS
 PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  