Plan Review Notes
Plan Review Notes For Permit 16060191
Permit Number 16060191
Review Stop B
Sequence Number 1
Notes
Date Text
2016-06-09 12:04:12BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060191
 ADD: 7320 S. DIXIE HWY.
 CONT: CAL DEVELOPMENT
 TEL: 954-564-0655/ 813-380-6930
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 09/2016
 ACTION: DENIED
  
 1) SHEET A00.40:
 1A) DETAIL 8 MOUNTING HEIGHTS, SHOWS LIGHT SWITCHES AND
 THERMOSTAT CENTER LINED AT 48 INCHES. PLEASE REVIEW
 2014 FBC-ACCESS. CODE 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. IN 308 UNOBSTRUCTED FORWARD AND SIDE
 APPROACH THE MAXIMUM FORWARD AND SIDE APPROACH BEING 48
 INCHES WOULD NEED TO BE THE TOP OF THE LIGHT SWITCH TO
 BE ABLE TO TURN THE SWITCH OFF AND ON.
  
 1B) THIS SAME DETAIL # 8 SHOWS THE HOLD UP LIGHT SWITCH
 AT 5?-0?. ARE YOU GOING TO DISCRIMINATE THAT A PERSON
 IN A WHEEL CHAIR CAN NOT ACTIVATE THIS DEVICE? 2014
 FBC-ACCESS. CODE 309.3 HEIGHT. OPERABLE PARTS SHALL BE
 PLACED WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED
 IN 308.
  
 1C)(1) SHEET A00.40 DETAIL # 6 SHOWS A SIGN FOR SIGNAGE
 A DIRECTIONAL SIGN FOR NON-ACCESSIBLE ENTRY. THIS SIGN
 DOES NOT HAVE BRAILLE INCORPORATED WITHIN THE SIGN.
 PLEASE REVIEW 2014 FBC-ACCESS. CODE 703.1 GENERAL.
 SIGNS SHALL COMPLY WITH 703. WHERE BOTH VISUAL AND
 TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN WITH
 BOTH VISUAL AND TACTILE CHARACTERS, OR TWO SEPARATE
 SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE
 CHARACTERS, SHALL BE PROVIDED.
  
 1C)(2) THE SECOND ISSUE WITH SIGNAGE IS ON SHEET A00.41
 DETAIL # 2. THIS DETAIL SHOWS SIGNAGE CENTER LINED AT
 5FT. THE BLOW UP DETAIL OF THAT SIGN DOES SHOW THAT
 BRAILLE & RAISED CHARACTERS ARE INCORPORATED INTO ONE
 SIGN. PLEASE REVIEW 2014 FBC-ACCESS. CODE 703.4.1
 HEIGHT ABOVE FINISH FLOOR OR GROUND & FIGURE 703.4.1
 HEIGHT OF TACTILE CHARACTERS ABOVE FINISH FLOOR OR
 GROUND.
  
 1D) DETAIL 4 (SIDE PROFILE) GRAB BARS THE DETAIL IS
 SHOWN AS VERTICAL DIMENSIONS ARE TAKEN TO THE TOP OF
 THE GRAB BAR ESCUTCHEON NOT THE TOP OF THE GRIPPING
 SURFACE, SEE 2014 FBC-ACCESS. CODE 609.4. CHANGE FORM
 CENTERLINE DIMENSIONING!!!
  
 2A) SHEET A02.01 NOTE # 7 INDICATES DOORS TO ACCEPT NEW
 ACCESSIBLE DOOR HARDWARE. THIS SAME NOTE INDICATES SEE
 DOOR SCHEDULE FOR HARDWARE TYPE. SHEET A003.00 THE DOOR
 SCHEDULE DOES INDICATE VARIOUS HARDWARE GROUPS AND LOCK
 MODEL NUMBERS BUT NOT TYPE OF DOOR HANDLE. PLEASE
 REVIEW ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE
 PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4.
 ACCESS. CODE 309.4 OPERATION. OPERABLE PARTS SHALL BE
 OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 (22.2 N) MAXIMUM.
  
 2B) NOTE THE ONLY DOOR SHOWING CODE COMPLIANCE WITH
 ACCESS. CODE 404.2.10 DOOR AND GATE SURFACES
 IS THE RESTROOM DOOR. PLEASE PROVIDE CODE COMPLIANCE
 WITH 2014 ACCESS. CODE 404.2.10 DOOR AND GATE SURFACES.
 SWINGING DOOR AND GATE SURFACES WITHIN 10 INCHES (255
 MM) OF THE FINISH FLOOR OR GROUND MEASURED VERTICALLY
 SHALL HAVE A SMOOTH SURFACE ON THE PUSH SIDE EXTENDING
 THE FULL WIDTH OF THE DOOR OR GATE. PARTS CREATING
 HORIZONTAL OR VERTICAL JOINTS IN THESE SURFACES SHALL
 BE WITHIN 1/16 INCH (1.6 MM) OF THE SAME PLANE AS THE
 OTHER. CAVITIES CREATED BY ADDED KICK PLATES SHALL BE
 CAPPED.
  
 3) SHEET C02.01;
 3A) THIS PLANS SHOWS 2 NEW ACCESSIBLE PARKING SPACES.
 WITH 74 LINEAR FEET OF NEW ASPHALT. THE PLAN DOES NOT
 PROVIDE ELEVATIONS OF THE ACCESSIBLE PARKING SPACE AND
 OF THE ACCESS AISLE, PLEASE SHOW COMPLIANCE WITH 2014
 FBC-ACCESS. CODE 502.4 FLOOR OR GROUND SURFACES.
 PARKING SPACES AND ACCESS AISLES SERVING THEM SHALL
 COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME
 LEVEL AS THE PARKING SPACES THEY SERVE. CHANGES IN
 LEVEL ARE NOT PERMITTED.
 EXCEPTION: SLOPES NOT STEEPER THAN 1:48 SHALL BE
 PERMITTED.
 ADVISORY 502.4 FLOOR OR GROUND SURFACES.
 ACCESS AISLES ARE REQUIRED TO BE NEARLY LEVEL IN ALL
 DIRECTIONS TO PROVIDE A SURFACE FOR WHEELCHAIR TRANSFER
 TO AND FROM VEHICLES. THE EXCEPTION ALLOWS SUFFICIENT
 SLOPE FOR DRAINAGE. BUILT-UP CURB RAMPS ARE NOT
 PERMITTED TO PROJECT INTO ACCESS AISLES AND PARKING
 SPACES BECAUSE THEY WOULD CREATE SLOPES GREATER THAN
 1:48.
  
 3B) THIS PLAN SHOWS THE NEW ACCESSIBLE PARKING SPACES
 AND ACCESS AISLES ON THE DIAGONAL. PLEASE SEE THE CITY
 OF WEST PALM BEACH MUNI CODE 94-485 FOR DIAGONAL
 ACCESSIBLE PARKING REQUIREMENTS.
 ACCESS. CODE 502.3.3 MARKING. ACCESS AISLES SHALL BE
 MARKED SO AS TO DISCOURAGE PARKING IN THEM.
 THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO
 DESIGNATE IT AS A NO-PARKING ZONE.
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED.
 FLORIDA LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL
 STRIPING OF ACCESS AISLES.
  
 4) SHEET C12.01 INDICATES A DOUBLE STRIPED ACCESSIBLE
 PARKING SPACE AND ACCESS AISLE. THE BLOWN UP DETAIL
 INDICATES A 4 INCH STIPE 2 INCHES BETWEEN STRIPES AND A
 SECOND 4 INCH STRIPE. PLEASE REVIEW CITY MUNI CODE
 94-485 FOR STRIPING DETAIL. ADVISORY 502.3.3 MARKING.
 THE METHOD AND COLOR OF MARKING ARE NOT SPECIFIED BY
 THESE REQUIREMENTS BUT MAY BE ADDRESSED BY STATE OR
 LOCAL LAWS OR REGULATIONS. BECAUSE THESE REQUIREMENTS
 PERMIT THE VAN ACCESS AISLE TO BE AS WIDE AS A PARKING
 SPACE, IT IS IMPORTANT THAT THE AISLE BE CLEARLY
 MARKED.
 FLORIDA LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL
 STRIPING OF ACCESS AISLES.
  
 5) SUBMITTED SURVEY IS A COPY NOT AN ORIGINAL. SEE
 FLORIDA STATUTE 472.025 SEALS/ S.S. 668.001-668.006.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  