| 2016-06-09 12:04:12 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16060191 |
| | ADD: 7320 S. DIXIE HWY. |
| | CONT: CAL DEVELOPMENT |
| | TEL: 954-564-0655/ 813-380-6930 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JUNE 09/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A00.40: |
| | 1A) DETAIL 8 MOUNTING HEIGHTS, SHOWS LIGHT SWITCHES AND |
| | THERMOSTAT CENTER LINED AT 48 INCHES. PLEASE REVIEW |
| | 2014 FBC-ACCESS. CODE 309.3 HEIGHT. OPERABLE PARTS |
| | SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| | SPECIFIED IN 308. IN 308 UNOBSTRUCTED FORWARD AND SIDE |
| | APPROACH THE MAXIMUM FORWARD AND SIDE APPROACH BEING 48 |
| | INCHES WOULD NEED TO BE THE TOP OF THE LIGHT SWITCH TO |
| | BE ABLE TO TURN THE SWITCH OFF AND ON. |
| | |
| | 1B) THIS SAME DETAIL # 8 SHOWS THE HOLD UP LIGHT SWITCH |
| | AT 5?-0?. ARE YOU GOING TO DISCRIMINATE THAT A PERSON |
| | IN A WHEEL CHAIR CAN NOT ACTIVATE THIS DEVICE? 2014 |
| | FBC-ACCESS. CODE 309.3 HEIGHT. OPERABLE PARTS SHALL BE |
| | PLACED WITHIN ONE OR MORE OF THE REACH RANGES SPECIFIED |
| | IN 308. |
| | |
| | 1C)(1) SHEET A00.40 DETAIL # 6 SHOWS A SIGN FOR SIGNAGE |
| | A DIRECTIONAL SIGN FOR NON-ACCESSIBLE ENTRY. THIS SIGN |
| | DOES NOT HAVE BRAILLE INCORPORATED WITHIN THE SIGN. |
| | PLEASE REVIEW 2014 FBC-ACCESS. CODE 703.1 GENERAL. |
| | SIGNS SHALL COMPLY WITH 703. WHERE BOTH VISUAL AND |
| | TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN WITH |
| | BOTH VISUAL AND TACTILE CHARACTERS, OR TWO SEPARATE |
| | SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE |
| | CHARACTERS, SHALL BE PROVIDED. |
| | |
| | 1C)(2) THE SECOND ISSUE WITH SIGNAGE IS ON SHEET A00.41 |
| | DETAIL # 2. THIS DETAIL SHOWS SIGNAGE CENTER LINED AT |
| | 5FT. THE BLOW UP DETAIL OF THAT SIGN DOES SHOW THAT |
| | BRAILLE & RAISED CHARACTERS ARE INCORPORATED INTO ONE |
| | SIGN. PLEASE REVIEW 2014 FBC-ACCESS. CODE 703.4.1 |
| | HEIGHT ABOVE FINISH FLOOR OR GROUND & FIGURE 703.4.1 |
| | HEIGHT OF TACTILE CHARACTERS ABOVE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 1D) DETAIL 4 (SIDE PROFILE) GRAB BARS THE DETAIL IS |
| | SHOWN AS VERTICAL DIMENSIONS ARE TAKEN TO THE TOP OF |
| | THE GRAB BAR ESCUTCHEON NOT THE TOP OF THE GRIPPING |
| | SURFACE, SEE 2014 FBC-ACCESS. CODE 609.4. CHANGE FORM |
| | CENTERLINE DIMENSIONING!!! |
| | |
| | 2A) SHEET A02.01 NOTE # 7 INDICATES DOORS TO ACCEPT NEW |
| | ACCESSIBLE DOOR HARDWARE. THIS SAME NOTE INDICATES SEE |
| | DOOR SCHEDULE FOR HARDWARE TYPE. SHEET A003.00 THE DOOR |
| | SCHEDULE DOES INDICATE VARIOUS HARDWARE GROUPS AND LOCK |
| | MODEL NUMBERS BUT NOT TYPE OF DOOR HANDLE. PLEASE |
| | REVIEW ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE. |
| | HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE |
| | PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4. |
| | ACCESS. CODE 309.4 OPERATION. OPERABLE PARTS SHALL BE |
| | OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| | (22.2 N) MAXIMUM. |
| | |
| | 2B) NOTE THE ONLY DOOR SHOWING CODE COMPLIANCE WITH |
| | ACCESS. CODE 404.2.10 DOOR AND GATE SURFACES |
| | IS THE RESTROOM DOOR. PLEASE PROVIDE CODE COMPLIANCE |
| | WITH 2014 ACCESS. CODE 404.2.10 DOOR AND GATE SURFACES. |
| | SWINGING DOOR AND GATE SURFACES WITHIN 10 INCHES (255 |
| | MM) OF THE FINISH FLOOR OR GROUND MEASURED VERTICALLY |
| | SHALL HAVE A SMOOTH SURFACE ON THE PUSH SIDE EXTENDING |
| | THE FULL WIDTH OF THE DOOR OR GATE. PARTS CREATING |
| | HORIZONTAL OR VERTICAL JOINTS IN THESE SURFACES SHALL |
| | BE WITHIN 1/16 INCH (1.6 MM) OF THE SAME PLANE AS THE |
| | OTHER. CAVITIES CREATED BY ADDED KICK PLATES SHALL BE |
| | CAPPED. |
| | |
| | 3) SHEET C02.01; |
| | 3A) THIS PLANS SHOWS 2 NEW ACCESSIBLE PARKING SPACES. |
| | WITH 74 LINEAR FEET OF NEW ASPHALT. THE PLAN DOES NOT |
| | PROVIDE ELEVATIONS OF THE ACCESSIBLE PARKING SPACE AND |
| | OF THE ACCESS AISLE, PLEASE SHOW COMPLIANCE WITH 2014 |
| | FBC-ACCESS. CODE 502.4 FLOOR OR GROUND SURFACES. |
| | PARKING SPACES AND ACCESS AISLES SERVING THEM SHALL |
| | COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME |
| | LEVEL AS THE PARKING SPACES THEY SERVE. CHANGES IN |
| | LEVEL ARE NOT PERMITTED. |
| | EXCEPTION: SLOPES NOT STEEPER THAN 1:48 SHALL BE |
| | PERMITTED. |
| | ADVISORY 502.4 FLOOR OR GROUND SURFACES. |
| | ACCESS AISLES ARE REQUIRED TO BE NEARLY LEVEL IN ALL |
| | DIRECTIONS TO PROVIDE A SURFACE FOR WHEELCHAIR TRANSFER |
| | TO AND FROM VEHICLES. THE EXCEPTION ALLOWS SUFFICIENT |
| | SLOPE FOR DRAINAGE. BUILT-UP CURB RAMPS ARE NOT |
| | PERMITTED TO PROJECT INTO ACCESS AISLES AND PARKING |
| | SPACES BECAUSE THEY WOULD CREATE SLOPES GREATER THAN |
| | 1:48. |
| | |
| | 3B) THIS PLAN SHOWS THE NEW ACCESSIBLE PARKING SPACES |
| | AND ACCESS AISLES ON THE DIAGONAL. PLEASE SEE THE CITY |
| | OF WEST PALM BEACH MUNI CODE 94-485 FOR DIAGONAL |
| | ACCESSIBLE PARKING REQUIREMENTS. |
| | ACCESS. CODE 502.3.3 MARKING. ACCESS AISLES SHALL BE |
| | MARKED SO AS TO DISCOURAGE PARKING IN THEM. |
| | THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO |
| | DESIGNATE IT AS A NO-PARKING ZONE. |
| | ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF |
| | MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY |
| | BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| | BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE |
| | TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT |
| | THE AISLE BE CLEARLY MARKED. |
| | FLORIDA LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL |
| | STRIPING OF ACCESS AISLES. |
| | |
| | 4) SHEET C12.01 INDICATES A DOUBLE STRIPED ACCESSIBLE |
| | PARKING SPACE AND ACCESS AISLE. THE BLOWN UP DETAIL |
| | INDICATES A 4 INCH STIPE 2 INCHES BETWEEN STRIPES AND A |
| | SECOND 4 INCH STRIPE. PLEASE REVIEW CITY MUNI CODE |
| | 94-485 FOR STRIPING DETAIL. ADVISORY 502.3.3 MARKING. |
| | THE METHOD AND COLOR OF MARKING ARE NOT SPECIFIED BY |
| | THESE REQUIREMENTS BUT MAY BE ADDRESSED BY STATE OR |
| | LOCAL LAWS OR REGULATIONS. BECAUSE THESE REQUIREMENTS |
| | PERMIT THE VAN ACCESS AISLE TO BE AS WIDE AS A PARKING |
| | SPACE, IT IS IMPORTANT THAT THE AISLE BE CLEARLY |
| | MARKED. |
| | FLORIDA LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL |
| | STRIPING OF ACCESS AISLES. |
| | |
| | 5) SUBMITTED SURVEY IS A COPY NOT AN ORIGINAL. SEE |
| | FLORIDA STATUTE 472.025 SEALS/ S.S. 668.001-668.006. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |