| Plan Review Notes For Permit 16060187 |
| Permit Number |
16060187 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-28 14:58:53 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF | | | THE NEW METAL ROOFING, ALUMINUM SIDING AND ALUMINUM | | | PREFORATED V-GROOVE SOFFIT. | | | | | | 2) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED | | | IN THE GAF PRODUCT APPROVAL (NOA NO. 14-1030.02) FOR AN | | | INSULATED ROOF AS SPECIFIED ON THE PLANS WILL BE USED. | | | SUBMIT TWO SETS OF RAS 117 CALCULATIONS FOR ENHANCED | | | FASTENING AS REQUIRED BY LIMITATION NUMBER 7 OF THE | | | NOA. | | | |
|