| Plan Review Notes For Permit 16060187 |
| Permit Number |
16060187 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-20 14:19:11 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) EXISTING BUILDING | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE 20" X 20" EXHAUST FAN. FBC-M | | | TABLE 403.3 REQUIRES A MINIMUM OF 200 CFMS FOR A TWO | | | CAR GARAGE. |
|