| 2016-06-20 10:45:56 | PLUMBING COMMENTS: | | | | | | 1. SHOW GRAB BARS IN SHOWER TO COMPLY WITH FBC ACC.SEC. | | | 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS. | | | IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE | | | PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A | | | POINT 18 INCHES (455 MM) FROM THE CONTROL WALL. | | | | | | 2. SHOW CONTROLS TO COMPLY WITH FBC ACC. SEC. 608.5.1 | | | TRANSFER TYPE SHOWER COMPARTMENTS. | | | IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS, | | | FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON | | | THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM) | | | MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE | | | SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL | | | 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE | | | SEAT TOWARD THE SHOWER OPENING. | | | | | | 3. SHOW SHOWER SEAT TO COMPLY WITH FBC ACC. SEC. 610.3 | | | SHOWER COMPARTMENT SEATS. IN TRANSFER-TYPE SHOWERS, THE | | | SEAT SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN | | | 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. SEATS SHALL | | | COMPLY WITH 610.3.1 OR 610.3.2. | | | | | | 4. SHOW ELEVATION DIMENSIONS OF WATER FOUNTAIN THEY | | | SHALL COMPLY WITH FBC ACC. SEC 306.2-306.3-307 | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | |
|