| 2016-10-26 12:54:04 | 2ND REVIEW | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE OVERFLOW SCUPPER THAT IS PART OF THE PRIMARY | | | DRAIN COLLECTOR BOX DOES NOT COMPLY WITH FBC PL SEC | | | 1108. A TOTALLY SEPARATE SECONDARY "OVERFLOW DRAIN" | | | WITH A SEPARATE OPENING IN PARAPET WALL IS REQUIRED. | | | PER FBC PL SEC 1108.2 AND SHALL COMPLY WITH FBC SEC | | | 1503.4.2.1 -1503.7 | | | | | | |
|