2016-11-04 14:12:14BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060181
 ADD: 1301 MERCER AVE.
 CONT: STOR-ALL CONSTRUCTION
 TEL: 561-966-0056
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: FRI. NOV. 04/ 2016
 ACTION: DENIED
  
 1) SEMI-COMPLIED. DOCUMENTATION FOR THE VALUE OF THE
 COST ASSOCIATED WITH THE BUILDING HAS BEEN AGREED WITH
 THE BUILDING OFFICIAL ROBERT BROWN. THE VALUE OF
 $8,597,303.00 ($78.19 SQ. FT.) WILL BE THE ASSESSED
 VALUE FOR THE BUILDING. PLEASE NOTE THE MECHANICAL,
 ELECTRICAL, PLUMBING AND ROOFING PERMIT VALUES ARE
 INCORPORATED INTO THE MASTER/ PRIME PERMIT. THERE WILL
 BE A $80.00 ADMINISTRATIVE FEE FOR THESE SUB-PERMITS IF
 THEY WERE NOT GENERATED AT THE ORIGINAL PERMIT
 SUBMITTAL TIME.
 ALL OTHER SUB-PERMITS ASSOCIATED WITH THIS BUILDING,
 LOW VOLTAGE, FIRE ALARM, FIRE SPRINKLER, ETC? PLEASE
 PROVIDE AN ITEMIZED LIST OF TYPE OF PERMIT AND VALUE OF
 THE CONTRACTS. PLEASE DEDUCT THESE VALUES FROM THE
 VALUE OF $8,597,303.00 THIS ADJUSTED VALUE WILL BE THE
 VALUE WE WILL USE ONCE THE UNKNOWNS ARE PROVIDED. THE
 BUILDING DEPARTMENT DOES NOT WANT TO DOUBLE DIP IN THE
 PERMIT FEES.
  
 2) THIS BUILDING BEING A 5 STORY BUILDING IS CONSIDERED
 A THRESHOLD BUILDING. / FL S. S. 553.71(7) THRESHOLD
 BUILDING MEANING ANY BUILDING WHICH IS GREATER THAN (3)
 STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY CLASSIFICATION AS DENIED IN THE FLORIDA
 BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND
 AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A)2ND REQUEST FOR A WRITTEN THRESHOLD INSPECTION PLAN,
 IT WAS NOT INCLUDED IN THE SUBMITTED DOCUMENTS NOR PART
 OF THE STRUCTURAL NOTES ON SHEETS SS0.0 & S0.1.
 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B)SEMI-COMPLIED. THRESHOLD INSPECTION FORMS. SHEET 3OF
 6 THE SPECIAL INSPECTOR D. MARK LEBLANC P.E. HAS SIGNED
 ON AS THE JOBSITE INSPECTOR. WITHIN THE SUBMITTED
 THRESHOLD INSPECTION FORMS THERE ARE DOCUMENTS FOR
 BRETT S ROSE BN5798, DOUGLAS JOSEPH RICHARD BN6661 AND
 PEDRO LUIS BOURG BN4952. IF THESE (3) INSPECTORS ARE
 GOING TO DO JOBSITE INSPECTIONS UNDER YOUR DIRECTION,
 THEN EACH OF THESE INSPECTORS WILL NEED TO SIGN PAGE 3
 OF 6 FOR JOBSITE INSPECTORS.
 1ST ROUND COMMENTS. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
 2C) COMPLIED. THRESHOLD BLDG., STATEMENT/ 633 FLORIDA
 STATUTE.
 2D) NOT REQUIRED. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS..
 2E)SEMI-COMPLIED. THE ONLY INSPECTOR THAT HAS NOT
 WORKED IN THE THRESHOLD PROGRAM IN THE CITY OF WEST
 PALM BEACH IS PEDRO LUIS BOURG. REQUIRED RESUME? HAS
 NOT BEEN SUBMITTED.
 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'
  
 2F) COMPLIED. CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2G) SEMI- COMPLIED. THREE SETS OF PLANS SUBMITTED, IN
 AT LEAST ONE SET OF PLANS THERE ARE MISSING PLANS,
 SHEETS : A-2.1, A-2.2, A-2.3, A-3.1, A-3.2, A-3.3 &
 A-3.4.
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2H)NOTICE ONLY!!! NO ACTION IS REQUIRED. PLEASE CALL
 THE CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 2I) NOTICE ONLY!!! NO ACTION IS REQUIRED. 109.3.6
 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3-14) COMPLIED.
 15)2ND REQUEST. THIS REVIEW F. I. E. ENGINEERING &
 TESTING LABS ROOF CALCULATIONS WERE TAKEN FOR AN
 EXPOSURE C. THE JOBSITE LOCATION IS AN EXPOSURE D. BOTH
 THE STRUCTURAL SHEETS AND ENGINEERING SHEETS FROM
 ORIGINAL COMMENT. THE ROOFING PRODUCT APPROVAL
 SUBMITTED FL -16730 GAF SINGLE PLY SYSTEM. NO
 SUB-SYSTEM WAS CIRCLED W/ ASSOCIATED PREUSSRES, MAY
 REQUIRE ENHANCED FASTENING.
  
 16) 11/09/2016 I SPOKE WITH TOMMY HOBGOOD ABOUT THE
 POSSIBILITY OF A STRUCTURE ONLY PERMIT. THE COMPONENTS
 AND CLADDING WOULD BE ABLE TO BROUGHT IN UNDER THE
 BUILDING PERMIT. DURING THIS TIME WE WOULD BE GETTING
 SHOP DRAWINGS FOR THE SECONDARY FRAMING MEMBERS FOR THE
 WALLS AND ROOF FRAMING MEMBERS,
  
 11/04/2016.TO DATE THERE HAS BEEN NO SHOP DRAWINGS,
 ELEVATIONS OR VIEW OF THE ROOF SHOWING THE SPACING
 BETWEEN THE STRUCTURAL STEEL COLUMNS AND BEAMS OR THE
 PURLINS AND GIRTS FOR ZONES 1,2,3 4 & 5. THIS WILL NEED
 TO BE ENGINEERED DRAWINGS SINCE THE GIRTS AND PURLINS
 ARE SECONDARY FRAMING MEMBERS OF THE BUILDING. SPACING
 OF THE GIRTS AND PURLINS IS CRITICAL TO THE REVIEW OF
 THE PRODUCT APPROVALS FOR COMPONENTS AND CLADDING. BOLT
 LAYOUT FOR THE ANCHORAGE OF THE VERTICAL STEEL COLUMNS
 TO THE FOUNDATIONS, AND CENTER TO CENTER OF COLUMNS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 BUILDING ENVELOPE
 STRUCTURAL CALCULATIONS (IF REQUIRED)
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
  
 17A) ENGINEERING CALCULATIONS REVISION # 6 MBCI METAL
 ROOF AND WALL SYSTEMS ENGINEERING REPORT IS NOT SIGNED
 NOR SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS.
  
 17B) ENGINEERING CALCULATIONS REVISION # 6 MBCI METAL
 ROOF AND WALL SYSTEMS ENGINEERING REPORT CONSISTING OF
 (8) PAGES WILL ALSO NEED TO SHOW COMPLIANCE WITH
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET.
  
 18) PLEASE PROVIDE SPAN CHARTS FOR THE TYPE OF DECKING
 THAT WILL BE INSTALLED ON FLOORS 2-5 AND ALLOWABLE
 LOADS. PLEASE ALSO SEE SHEETS S2.1-S2.5 THERE IS AN
 ALTERNATE USE OF DECKING MATERIAL UNDER NOTE # 1.
 PLEASE SEE 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION. NO ALTERNATES. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 19) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 20) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  