| 2016-08-23 11:29:35 | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | PLUMBING COMMENTS: 2ND REVIEW |
| | |
| | 2ND REQUEST |
| | |
| | 5. NOT COMPLIED SHOW CLEAR FLOOR SPACE FOR WATER |
| | FOUNTAIN SHALL COMPLY WITH FBC ACC 602.2 CLEAR FLOOR |
| | SPACE. |
| | UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | SHT A4.4 SHOWS A PARALLEL APPROACH IT SHALL BE A |
| | FORWARD APPROACH. |
| | |
| | 10.NOT COMPLIED PROVIDE MANUFACTURE SPECIFICATIONS FOR |
| | TANKLESS HEATERS AND ELEVATOR SUMP PIT OIL SMART PUMP. |
| | PER PB AMEND. TO FBC SEC. 107.2.1 |
| | SHOW NOTE ON PLAN TO PROVIDE MANUFACTURE SPECS AND |
| | INSTILLATION GUIDES ON JOBSITE FOR INSPECTIONS. |
| | |
| | 12.NOT COMPLIED PROVIDE SLOPE OF HORIZONTAL STORM DRAIN |
| | SHALL COMPLY WITH FBC PL TABLE 1106.3 |
| | SHT. P1 YOU PROVIDED A NOTE REFERENCING THE TABLE BUT |
| | YOU DID NOT LIST WHICH ONE OUT OF THE THREE SLOPES WAS |
| | BEING USED. |
| | |
| | NEW COMMENTS |
| | 1. THE FLOOR SINK FOR ELEVATOR SUMP PIT DRAINS IS NOT |
| | VENTED. PER 901.2.1 VENTING REQUIRED. |
| | TRAPS AND TRAPPED FIXTURES SHALL BE VENTED IN |
| | ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN |
| | THIS CHAPTER. |
| | |
| | 2. SHT P8 INCLUDE THE FLOOR SINK ON YOUR NOTE FOR THE |
| | TRAP PRIMERS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. THE LAVATORY FAUCETS IN THE BATHROOMS SHA HAVE A |
| | TEMPERATURE LIMITING DEVICE TO COMPLY WITH FBC PL 416.5 |
| | TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | 607.1.1 TEMPERATURE LIMITING MEANS. |
| | A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE |
| | AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF |
| | COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR |
| | MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY |
| | TEMPERATURE AT FIXTURES. |
| | |
| | 4. SHT. P4 SHOWS 1IN CW FROM 3RD FLOOR TO BATHROOMS SHT |
| | P8 WATER RISER SHOWS 3/4 FROM 3RD FLOOR TO BATHROOMS |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. THE SPOUT FOR THE EMERGENCY ROOF DRAIN SHALL |
| | DISCHARGE A MIN. OF 12IN FROM BUILDING. PER FBC 1503.7 |
| | |
| | SEPARATE PERMIT REQUIRED FOR BACKFLOWS |
| | |
| | DOCUMENTATION REQUIRED FOR BACKFLOW PREVENTION DEVICE |
| | PERMITS |
| | |
| | EFFECTIVE DATE: JANUARY 4TH, 2016 |
| | |
| | THE PERMIT APPLICATION SHALL BE SUBMITTED WITH THE |
| | FOLLOWING DOCUMENTATION: |
| | |
| | 1) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR |
| | THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE |
| | DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK |
| | SECTION ON THE PERMIT APPLICATION. |
| | |
| | 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE. |
| | |
| | 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF |
| | SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES. |
| | 4) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO |
| | CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE |
| | CITY?S REQUIREMENTS. |
| | 5) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED |
| | IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND |
| | CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES |
| | DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH |
| | PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO |
| | ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE |
| | DEVICE. |
| | NOTE: THE PERMIT CARD AND MANUFACTURER?S SPECIFICATIONS |
| | SHALL BE ON THE JOBSITE FOR INSPECTION. |
| | PLEASE REFER TO THE ATTACHED DOCUMENT FOR INFORMATION |
| | REGARDING THE CITY OF WEST PALM BEACH APPROVED |
| | CONTRACTOR?S LIST FOR CERTIFYING / RECERTIFYING |
| | BACKFLOW DEVICES. |
| | THE ESTIMATED REVIEW TIME FOR THESE PERMITS IS |
| | APPROXIMATELY 72 HOURS. |
| | THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL |
| | MANUAL CAN BE FOUND AT : |
| | HTTP://WPB.ORG/UTILITIES/BACKFLOW |
| | UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS: |
| | WWW.USC.EDU/DEPT/FCCCHR |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |