Plan Review Notes
Plan Review Notes For Permit 16060181
Permit Number 16060181
Review Stop M
Sequence Number 2
Notes
Date Text
2016-08-03 16:25:272ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16060181
 8/3/16
  
 COMMENTS #1-4 FROM THE 1ST REVIEW STILL EXIST. I HAVE
 REPRINTED THEM BELOW WITH SOME MODIFICATIONS BASED ON
 THIS 2ND REVIEW.
  
 1) COMMISSIONING OF THE AC SYSTEMS IS REQUIRED IN
 ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY
 CONSERVATION. SUBMIT A COMMISSIONING PLAN IN COMPLIANCE
 WITH C408.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) THE COMPLIANCE DATA FOR THE AC SYSTEMS (AC
 IDENTIFICATIONS, AND CAPACITIES) LISTED ON PAGE 6 OF
 THE ENERGY GAUGE PERFORMANCE SUBMITTAL DO NOT MATCH THE
 SCHEDULES ON SHEET M8.
  
 3) ENERGY GAUGE SUBMITTAL, PAGE 2 CERTIFICATIONS: THE
 ARCHITECT OF RECORD MUST PROVIDE HIS REGISTRATION
 NUMBER ON THE PAGE.
  
 4) REFER TO SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION: THE CAPACITIES OF THE DAIKIN AC SYSTEMS
 SPECIFIED FOR THE 1ST- 4TH FLOOR WAREHOUSE AREAS ARE
 EXCEEDING THE CALCULATED LOADS SHOWN IN THE SIZING
 SUMMARRIES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  