| Plan Review Notes For Permit 16060181 |
| Permit Number |
16060181 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-08-04 13:59:23 | 1301 MERCER AVENUE | | | PERMIT #16060181 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FIRE PROTECTION SHEETS FP-61G NOT SUBMITTED. | | | | | | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE | | | REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE | | | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN | | | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED | | | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. FOR ISSUANCE | | | OF A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF | | | THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE | | | PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR | | | ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER | | | FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE | | | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|