Plan Review Notes
Plan Review Notes For Permit 16060181
Permit Number 16060181
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2016-08-04 13:59:231301 MERCER AVENUE
 PERMIT #16060181
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SHEETS FP-61G NOT SUBMITTED.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. FOR ISSUANCE
 OF A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF
 THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE
 PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR
 ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  