| 2016-06-23 14:15:20 | 1ST REVIEW |
| | |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE |
| | FACILITIES SHALLL BE PROVIDED FOR EACH SEX.BATHROOM |
| | FACILITIES ARE NOT REQUIRED ON THE SECOND FLOOR YOU CAN |
| | PROVIDE SEPARATE FACILITIES ON FORTH FLOOR TO COMPLY |
| | WITH THIS CODE . PER BC PL SEC.403.2 |
| | |
| | 2. SHT. A-1 SHOWS A BATHROOM ON THIRD FLOOR SHT.-.03 |
| | PLUMBING FIXTURE REQUIREMENTS SHOWS A BATHROOM ON THE |
| | THIRD FLOOR . THE REST OF THE PLAN SHOWS BATHROOMS ON |
| | THE SECOND AND FORTH FLOORS PLEASE CLARIFY. PER PB |
| | AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 3. SHOW CLEAR FLOOR SPACE FOR WATER CLOSETS SHALL |
| | COMPLY WITH. FBC ACC 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 4. SHOW CLEAR FLOOR SPACE FOR WALL HUNG LAVATORIES |
| | SHALL COMPLY WITH FBC ACC 606.2 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR |
| | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 5. SHOW CLEAR FLOOR SPACE FOR WATER FOUNTAIN SHALL |
| | COMPLY WITH FBC ACC 602.2 CLEAR FLOOR SPACE. |
| | UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 6. DOOR SWING IN BATHROOM S SHALL COMPLY WITH FBC ACC |
| | 603.2.3 DOOR SWING. |
| | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| | CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE |
| | PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. |
| | EXCEPTIONS: |
| | 2. WHERE THE TOILET ROOM OR BATHING ROOM IS FOR |
| | INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH |
| | 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE |
| | DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE |
| | CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY |
| | FIXTURE. |
| | |
| | 7. TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC |
| | 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. |
| | |
| | 8. GRAB BARS SHAL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE TO FINISHED FLOOR NOT FROM THE CENTER |
| | OF THE BAR. PER FBC ACC 609.4 |
| | |
| | 9. CIVIL PLAN SHOWS A 1IN WATER SERVICE SHT. P SHOWS AN |
| | 11/4IN WATER SERVICE PLEASE CLARIFY. PER PB AMEND. TO |
| | FBC SEC. 107.2.1 |
| | |
| | 10. PROVIDE MANUFACTURE SPECIFICATIONS FOR TANKLESS |
| | HEATERS AND ELEVATOR SUMP PIT OIL SMART PUMP. PER PB |
| | AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 11. SHOW ROOF TOP HOSE BIBS ON RISER DIAGRAM AND PLAN |
| | VIEW. PER PB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 12. PROVIDE SLOPE OF HORIZONTAL STORM DRAIN SHALL |
| | COMPLY WITH FBC PL TABLE 1106.3 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |