Plan Review Notes
Plan Review Notes For Permit 16060181
Permit Number 16060181
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-25 13:37:51INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL
 SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE WILL
 SUFFICE.
 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR FIRE PUMP AND ALL LOW VOLTAGE SYSTEMS TO INCLUDE
 BUT NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS, CCTV,
 PHONE AND DATA, SIGNAGE, WIRELESS SYSTEMS, CAR CHARGING
 STATIONS, ETC. A NOTE WILL SUFFICE.
 3. PLEASE LABEL RECEPTACLE IN WORK ROOM TO BE GFCI
 PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF SINK ALL TO
 BE GFCI. SEE E1 OFFICE AREA
 4. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL
 AVAILABLE FAULT CURRENT AT THE TRANSFORMERS. FBC
 107.3.5
 5. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5
 6. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC
 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS.
 7. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS
 FOR FEEDERS AND BRANCH CIRCUITS.
 8. ADDRESS FIRE, MECH AND PLUMBING REVIEWS REGARDING
 ELECTRICAL REQUIREMENTS. FBC 107.3.5
 9. LABEL 1000AMP MAIN TO BE GFCI PROTECTED PER NEC
 240.13
 10. PROVIDE PHOTOMETRICS FOR ALL AREAS TO SHOW MINIMUM
 LIGHTING LEVELS. FBC 107.3.5
 11. PROVIDE A NOTE AT THE RISER DIAGRAM FIRE PUMP
 CONTROLLER TO RATED FOR SERVICE ENTRANCE.
 12. SHOW LOCATION OF PANEL AC, AT ELECTRICAL ROOM
 LOCATION. PROVIDE A NOTE TO COMPLY WITH TAP RULES PER
 NEC 240.21B
 13. AT TRANSFORMER RATED 112.5 SIZE GROUNDING ELECTRODE
 CONDUCTOR PER NEC 250.66 TABLE/ 1/0CU.
 14. SHOW A GFCI RECEPTACLE AT THE ELEVATOR MACHINE
 ROOM/ ELEVATOR EQUIPMENT PER NEC 620.23. ALSO A
 DEDICATED BRANCH TO BE PROVIDED EXCLUSIVELY TO ROOM.
 CIRCUIT H-9 SHOWN FEEDING OTHER AREAS, CORRECT AND
 ADDRESS AT PANEL SCHEDULE ALSO.
 15. PROVIDE A NOTE TO COMPLY WITH FBC ENERGY
 CONSERVATION 2014- 50% OF RECEPTACLES TO BE
 AUTOMATICALLY CONTROLLED PER CODE SECTION FBC C405.7.
 SHOW COMPLIANCE.
 16. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  