| 2016-06-25 13:37:51 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | |
| | 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL |
| | SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE WILL |
| | SUFFICE. |
| | 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS |
| | FOR FIRE PUMP AND ALL LOW VOLTAGE SYSTEMS TO INCLUDE |
| | BUT NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS, CCTV, |
| | PHONE AND DATA, SIGNAGE, WIRELESS SYSTEMS, CAR CHARGING |
| | STATIONS, ETC. A NOTE WILL SUFFICE. |
| | 3. PLEASE LABEL RECEPTACLE IN WORK ROOM TO BE GFCI |
| | PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF SINK ALL TO |
| | BE GFCI. SEE E1 OFFICE AREA |
| | 4. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL |
| | AVAILABLE FAULT CURRENT AT THE TRANSFORMERS. FBC |
| | 107.3.5 |
| | 5. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5 |
| | 6. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC |
| | 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE |
| | DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS. |
| | 7. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS |
| | FOR FEEDERS AND BRANCH CIRCUITS. |
| | 8. ADDRESS FIRE, MECH AND PLUMBING REVIEWS REGARDING |
| | ELECTRICAL REQUIREMENTS. FBC 107.3.5 |
| | 9. LABEL 1000AMP MAIN TO BE GFCI PROTECTED PER NEC |
| | 240.13 |
| | 10. PROVIDE PHOTOMETRICS FOR ALL AREAS TO SHOW MINIMUM |
| | LIGHTING LEVELS. FBC 107.3.5 |
| | 11. PROVIDE A NOTE AT THE RISER DIAGRAM FIRE PUMP |
| | CONTROLLER TO RATED FOR SERVICE ENTRANCE. |
| | 12. SHOW LOCATION OF PANEL AC, AT ELECTRICAL ROOM |
| | LOCATION. PROVIDE A NOTE TO COMPLY WITH TAP RULES PER |
| | NEC 240.21B |
| | 13. AT TRANSFORMER RATED 112.5 SIZE GROUNDING ELECTRODE |
| | CONDUCTOR PER NEC 250.66 TABLE/ 1/0CU. |
| | 14. SHOW A GFCI RECEPTACLE AT THE ELEVATOR MACHINE |
| | ROOM/ ELEVATOR EQUIPMENT PER NEC 620.23. ALSO A |
| | DEDICATED BRANCH TO BE PROVIDED EXCLUSIVELY TO ROOM. |
| | CIRCUIT H-9 SHOWN FEEDING OTHER AREAS, CORRECT AND |
| | ADDRESS AT PANEL SCHEDULE ALSO. |
| | 15. PROVIDE A NOTE TO COMPLY WITH FBC ENERGY |
| | CONSERVATION 2014- 50% OF RECEPTACLES TO BE |
| | AUTOMATICALLY CONTROLLED PER CODE SECTION FBC C405.7. |
| | SHOW COMPLIANCE. |
| | 16. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |