2016-07-11 15:39:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16060181
 ADD: 1301 MERCER AVE.
 CONT: STOR-ALL CONSTRUCTION
 TEL: 561-966-0056
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. JUNE 11/ 2016
 ACTION: DENIED
  
 1) THE BUILDING VALUATION IS LOW FOR THE BUILDING TYPE
 AND OCCUPANCY. THE JUNE 2016 IIC TABLES LIST THE VALUE
 OF THIS PROJECT AT $9,880,466.00 DOLLARS. 109,954 SQ.
 FT. X $89.86= $9,880,466.00.
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THIS BUILDING BEING A 5 STORY BUILDING IS CONSIDERED
 A THRESHOLD BUILDING. / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2E) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'
  
 2F) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2G) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 3) SHEET S0.0. PROVIDES THE WIND DESIGN CRITERIA. THE
 EXPOSURE IS LISTED AS A ?C? EXPOSURE. EXPOSURES FOR THE
 BUILDING ARE TAKEN FOR THE WORST CASE SCENARIO. THERE
 IS OVER 5000 FEET OF WATER TO THE NORTH AND NNW MEETING
 THE DEFINITION OF EXPOSURE D. 1609.4 EXPOSURE CATEGORY.
 1609.4.3 EXPOSURE CATEGORIES.
 AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE
 WITH THE FOLLOWING: EXPOSURE D. EXPOSURE D SHALL APPLY
 WHERE THE GROUND SURFACE ROUGHNESS, AS DEFINED BY
 SURFACE ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION
 FOR A DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20
 TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER.
 EXPOSURE D SHALL ALSO APPLY WHERE THE GROUND SURFACE
 ROUGHNESS IMMEDIATELY UPWIND OF THE SITE IS B OR C, AND
 THE SITE IS WITHIN A DISTANCE OF 600 FEET (183 M) OR 20
 TIMES THE BUILDING HEIGHT, WHICHEVER IS GREATER, FROM
 AN EXPOSURE D CONDITION AS DEFINED IN THE PREVIOUS
 SENTENCE.
  
 4) WITH THE PRESSURES GIVEN ON SHEET S0.1 THE PRESSURES
 WILL BE HIGHER SEE THE 2014 FBC-B TABLE 1609.7(2)
 ADJUSTMENT FACTOR FOR BUILDING HEIGHT AND EXPOSURE,
 (?). 55FT./ EXPOSURE D ADJUSTMENT FACTOR OF 1.84.
 PRESSURES WILL NEED TO BE RECALCULATED.
  
 5) SHEET S0.1 THE CHART FOR COMPONENTS & CLADDING
 PRESSURES THERE ARE ROOF ZONES 1 FOR THE INTERIOR ZONE
 AND WHAT APPEARS TO BE TWO ZONE 3 CATEGORIES, NO
 PERIMETER ZONE # 2? ASCE 7-10 FIGURE 30.5.1 .
  
 6) SHEET S0.1 PLEASE PROVIDE THE COMPONENT AND CLADDING
 IN VULT AND IN VASD. ALL OF THE PRODUCT APPROVALS ARE
 IN VASD, THE INSPECTORS IN THE FIELD NEED THE PLANS IN
 VASD TO MATCH THE PRODUCT APPROVAL. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 7) PLEASE NOTE THERE IS NO DOOR SCHEDULE LISTED IN THE
 DRAWING INDEX AND ON SHEET A5.3 IN THE HARDWARE
 SCHEDULE NEITHER EXIT STAIR TOWER 1 OR 2 DOOR HARDWARE
 SHOW A FIRE RATING . SEE 2014 FBC-B 1009.3.1.2.
 STAIRWELL 4 STORIES AND MORE REQUIRE A 2 HR. FIRE
 RATING AND TABLE 716.5 REQUIRES 1 ? HOUR PROTECTIVES.
  
 8) SHEET A-1.1 SHOWS THE ELEVATOR MACHINE ROOM AND THE
 ELECTRICAL ROOM AS 2 HOUR FIRE RATING, AGAIN NO DOOR
 SCHEDULE, REQUIRES 1 ? HOUR PROTECTIVE FOR A 2 HOUR
 RATED WALL. 2014 FBC-B TABLE 716.5.
  
 9A) SHEETS A-4.5 & A-4.6 BOTH SHOW A SIDE VIEW OF THE
 STAIRWELLS. THE 1ST FLOOR OF THE STAIR IN BOTH
 STAIRWELLS DOES NOT SHOW COMPLIANCE WITH: 2014
 FBC-ACCESSIBILITY CODE 307.4 AND FIGURE 307.4.
  
 9B) BOTH SHEETS A-4.5 & A-4.6 SHOW THE RISE AND RUN OF
 THE STAIRS, BUT PLANS DO NOT INDICATE IF THE STAIRS ARE
 TO HAVE SOLID RISERS. FBC-B 101009.7.5.3.
  
 9C) SHEETS A-4.5 & A-4.6 NEITHER SHOW COMPLIANCE WITH
 FBC-B 905.4. LOCATION OF CLASS I STANDPIPE(1) IN EVERY
 REQUIRED STAIRWAY.
  
 10) SHEET A-1.1 THE ELEVATOR CAB DOES NOT INDICATE WITH
 STRETCHER REQUIREMENTS, SEE FBC-B 3002.4 ELEVATOR CARS
 TO ACCOMMODATE AMBULANCE STRETCHERS.
  
 11) SHEET A-4.5 DETAIL 4 INDICATES WHAT APPEARS TO BE A
 HYDRAULIC ELEVATOR, PLEASE PROVIDE COMPLIANCE WITH
 FBC-B 3011.1 ELECTROLYSIS PROTECTION FOR UNDERGROUND
 HYDRAULIC ELEVATOR CYLINDERS.
 12) BOTH A-1.6 AND M6 SHOWS ROOF TOP COMPRESSORS ON TOP
 OF A/C STANDS. PLEASE SUBMIT THE PRODUCT APPROVAL FOR
 THE ROOF TOP STANDS. PROVIDE ANCHORING FOR THE STAND AS
 WELL AS THE UNIT TO THE STAND. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(G) PRE-ENGINEERED A/C STANDS.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 13) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN PROFESSIONAL
 IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE FOR
 REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS PREPARED
 BY OTHERS, INCLUDING PHASED AND DEFERRED SUBMITTAL
 ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF THE
 BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 14) SHEET A-0.3 INDICATES THIS BUILDING IS TO BE FIRE
 SPRINKLERED AND TO TAKE A ONE STORY INCREASE. NO FIRE
 SPRINKLER PLANS WERE SUBMITTED. 105.3.1.2 NO PERMIT MAY
 BE ISSUED FOR ANY BUILDING CONSTRUCTION,(2) FIRE
 SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR ADDITION
 WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS
 50 OR MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR
 II OR CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521,
 FLORIDA STATUTES, MAY DESIGN A FIRE SPRINKLER SYSTEM OF
 49 OR FEWER HEADS AND MAY DESIGN THE ALTERATION OF AN
 EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION
 CONSISTS OF THE RELOCATION, ADDITION OR DELETION OF NOT
 MORE THAN 49 HEADS, NOTWITHSTANDING THE SIZE OF THE
 EXISTING FIRE SPRINKLER
 SYSTEM. ALSO REVIEW FLORIDA ADMINISTRATIVE CODE
 61G15-32.004
  
 15) THE ROOFING PRODUCT APPROVAL SUBMITTED FL -16730
 GAF SINGLE PLY SYSTEM. NO SUB-SYSTEM WAS CIRCLED W/
 ASSOCIATED PREUSSRES, MAY REQUIRE ENHANCED FASTENING.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  