| 2016-06-03 16:34:07 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- FLAT ROOF NOA 14-0529.02 SUBMITTED: | | | A) THE DESIGN PRESSURES ON SELECTED ASSEMBLY ON PAGE 24 | | | OF 42 ARE -52.5PSF. THE DESIGN PRESSURES FOR PERIMETER | | | AND CORNER ROOF AREAS ARE HIGHER. NEED TO PROVIDE | | | SIGNED AND SEALED RAS 117 CALCULATIONS (2 COPIES) AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN | | | PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL, 5TH | | | EDITION (2014). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | |
|